instabus EIB

 

Technical Product Information 

September 2001 

Time Switch 4 Channel REG 372 

5WG1 372-5AR01 

 

 

 

 

Siemens AG 

REG 372, 4 pages 

Technical Manual 

Product and Applications Description 

 

 

 
The time switch REG 372 is a DIN-rail mounted 
device laterally attached to the bus coupling unit 
REG 110 (to be ordered separately, order number: 
5WG1 110-5AR01). During this it occupies 4 address-
ing locations of the bus coupling unit. Via the four 
channels time controlled applications such as illumina-
tion, heating or shutters can be switched on or off. It 
can be used as daily, weekly or yearly clock controller. 
By connecting an aerial FA and a power unit NT DCF77 
the clock controller itself automatically sets the up-to-
date daytime and date (MEZ). 
With a reading button the set switching times, date 
referenced inputs and 1x-switching commands can be 
trialled. 
The bus coupling unit REG 110, the power unit 
NT DCF77 and the radio aerial FA are not contained in 
the volume of delivery and must be ordered separately 
 
 

Operational specifications 

• 

4 channels 

• 

response margin 

• 

radio interface DCF 77 

• 

date referenced input 

• 

single days and date ranges 

• 

free weekday and channel block establishment 

• 

yearly, weekly and daily program 

• 

322 memory locations 

• 

no double tasks of the push-buttons 

• 

automatic summer-/winter time conversion 

• 

possibility of setting the program: every minute 

• 

shortest switching time 1 minute 

• 

rapid impulse 

• 

preliminary selection (override) 

• 

switching condition permanent ON, permanent OFF 

 
 

Application Programs 

 

11 S4 Time switch 4 Channel 241A01 

• 

4 inputs for time switch 

• 

control start event  

• 

control finishing event  

• 

delayed on-switching 

• 

delayed off-switching 

• 

channel connection (AND/OR) 

 

Note  

Before programming the device has to be supplied with 
voltage for at least 6 minutes (charge the accumulator). 
 
 

Example of Operation  

 

PEI

bus
coupling
unit
REG 110

FA 

aerial DCF77

Frankfurt / Main

signal

-  +

- +

time clock controller REG 372

in

st

ab

us

 EI

B

power unit
NT
DCF 77

 

 
 

Installation Instructions 

 

• 

The device may be used for permanent interior 
installations in dry locations within high voltage 
distribution board or small casings. 

 

V

 WARNING 

• 

The device may be built into distribution boards 
(230/400V) together only with appropriate VDE-
devices and must be mounted and commissioned by 
an authorised electrician. 

• 

Free DIN rail areas must be covered with covers, 
order no. 5WG1 192-8AA01. 

• 

The prevailing safety rules must be heeded. 

• 

The device must not be opened. A device suspected 
faulty should be returned to the local Siemens office. 

Automation and Drives Group 

 

 

Electrical Installation Technology 

 Siemens AG 2001 

Update: http://www.siemens.de/installationstechnik 

P.O.Box 10 09 53, D-93009 Regensburg 

Subject to change without prior notice 

 

 

2.18.2.2/1 

Содержание 5WG1 372-5AR01

Страница 1: ...buttons automatic summer winter time conversion possibility of setting the program every minute shortest switching time 1 minute rapid impulse preliminary selection override switching condition permanent ON permanent OFF Application Programs 11 S4 Time switch 4 Channel 241A01 4 inputs for time switch control start event control finishing event delayed on switching delayed off switching channel con...

Страница 2: ...blishment summer wintertime conversion automatically holiday program yes Electrical safety fouling class according to IEC 664 1 2 protection according to EN 60529 IP 20 protection class according to IEC 1140 II overvoltage class according to IEC 664 1 III bus safety extra low voltage SELV DC 24 V device complies with EN 50 090 2 2 and IEC 664 1 1992 Electromagnetic compatibility complies with EN 5...

Страница 3: ...e slide C4 with a screw driver and click it into place by a slight pressure and swivel the device C1 from the DIN rail C3 C2 C1 C1 C3 C4 Figure 3 Dismounting the DIN rail device Connecting terminal line aerial FA Figure 4 Remove approx 5mm of the insulation of the conduc tor D1 1 plug it into the connection blocks D1 and tighten the screws D1 2 Connections aerial FA strip insulation for 5mm permis...

Страница 4: ...G 372 5WG1 372 5AR01 Notes Technical Manual REG 372 4 pages Siemens AG Automation and Drives Group Update http www siemens de installationstechnik Siemens AG 2001 Electrical Installation Technology Subject to change without prior notice P O Box 10 09 53 D 93009 Regensburg 2 18 2 2 4 ...

Отзывы: