background image

Document No. 570-136  
Installation Instructions  
October 26, 2016 

Page 4 of 11

 

Siemens Industry, Inc.

 

 

 

CAUTION 

It is important that the neutral that 

supplies the TEC must be earth 

grounded at the source of the 24 

Vac power. 
Possible erratic equipment 

operation or damage if neutral is not 

grounded. 

 

 

 

ATTENTION 

Il est très important que le neutre 

qui alimente le TEC soit mis à la 

terre à la source de l’alimentation  

24 Vca. 
Risque de fonctionnement 

incohérent de l’équipement ou de 

dégats si le neutre n’est pas mis à 

la terre. 

 

10.  For a Fast Acting Lab Electronic Actuator, 

verify that the switches are set as shown in 

Figure 

Switch Settings for the Fast Acting 

Lab Electronic Actuator

 

 

 

 

Damper 

Venturi Air Valve 

Switch Settings for the Fast Acting Lab Electronic 

Actuator.

 

 

 

The installation is complete.  

 

Dimensions. 

 

Smoke Control Compliance 

The following instructions and information apply if 

used for smoke control sequence. 

1.  Install Smoke Control Listed products, enclosure 

and transformer. See the 

Product Numbers

 and 

Accessories

 sections for more information.  

2.  Input Rating: 

–  24V 60 Hz 60 VA maximum 

3.  Digital Output (DO) are the only I/O authorized 

for smoke control applications. 

Digital Output (DO) Electrical Ratings: 

–  5 VA per DO/ maximum 40 VA total 

4.  The room temperature sensor (RTS) is installed 

in the same area as the TEC. 

5.  Connection from the TEC to the field panel is a 

maximum 4000 feet, 24 AWG minimum. 

6.  Wiring Range: 

–  Transformer: primary 14 AWG 
–  24 Vac Input Power: 14 to 18 AWG 
–  DO: AI: 18 to 20 AWG 
–  DI: 18 AWG 
–  LAN: 20 to 24 AWG 
–  RST: 24 AWG 
All circuits are power limited; FLN is RS-485, 

RTS is RS-232. Digital Inputs (DI) are dry 

contacts. 
See the following documents for more 

information on configuring smoke control 

applications: 

 

Smoke Control Systems Application and 

Engineering Manual (

125-1806) 

 

Smoke Control System Application Guide 

(

125-1816) 

 

NFPA and UL Standards Relevant to Smoke 

Control System Application Guide (

125-

1817) 

Содержание 570-00701PKA

Страница 1: ...nturi Air Valve to maintain control of a chemical fume hood with up to 2 sashes It uses fast acting electronic actuators shipped separately to control the exhaust control device WARNING The application cannot detect a broken wire to the analog input for the second sash An external sash aggregating device should be used to calculate the face area for all fume hoods with more than one sash This cont...

Страница 2: ...ne décharge électrostatique peut endommager la carte équipée Accessories Room Sensor Cable 25 ft Room Sensor Cable 50 ft 588 100A 588 100B Vertical Sash Sensor 50 inch range 80 inch range 546 04000 546 04001 Parts for Smoke Control Compliance Smoke Control Listed Large Equipment Controller Enclosure Long board and ATEC controllers 550 002K UL Listed Class 2 transformer with 120 240 277 480 Vac 50 ...

Страница 3: ...esired location 2 Place the ESD wrist strap on your wrist and attach it to a good earth ground 3 Remove the controller from the static proof bag and snap it into place on the mounting rail 4 If the controller will be used with a field panel disconnect the field level network FLN trunk from the field panel 5 Wire the FLN trunk to the controller After all controllers are connected to the FLN reconne...

Страница 4: ... and information apply if used for smoke control sequence 1 Install Smoke Control Listed products enclosure and transformer See the Product Numbers and Accessories sections for more information 2 Input Rating 24V 60 Hz 60 VA maximum 3 Digital Output DO are the only I O authorized for smoke control applications Digital Output DO Electrical Ratings 5 VA per DO maximum 40 VA total 4 The room temperat...

Страница 5: ...ful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient or relocate the receivin...

Страница 6: ...re to the analog input for the second sash An external sash aggregating device should be used to calculate the face area for all fume hoods with more than one sash AVERTISSMENT L application ne peut pas détecter un fil rompu allant à une entrée analogique pour le second châssis Un dispositif externe de cumulation de châssis devrait être utilisé pour calculer la surface à l entrée de toutes les hot...

Страница 7: ...en wiring any actuator that uses a 0 to 10V control signal and ties AC neutral to DC common an additional wire must connect the actuator AC neutral to the DC common of the PTEC TEC AO being used to control the actuator 24 Vac Modulating Control Actuator Symbol TEC Connection Function Terminal Connection Standard Color 1 H Supply SP G Red 2 C Neutral SN G0 Black 8 AO3 15 0 to 10V input signal Y Gra...

Страница 8: ...Document No 570 136 Installation Instructions October 26 2016 Page 8 of 11 Siemens Industry Inc Application 6740 Wiring Diagram ...

Страница 9: ...Document No 570 136 Installation Instructions October 26 2016 Siemens Industry Inc Page 9 of 11 Application 6741 Wiring Diagram ...

Страница 10: ...Document No 570 136 Installation Instructions October 26 2016 Page 10 of 11 Siemens Industry Inc Application 6742 Wiring Diagram ...

Страница 11: ...curity management and physical security systems The security functions on these products solutions and services are important components of a comprehensive security concept Drafting implementing and managing a comprehensive and up to date security concept customized to individual needs is nevertheless necessary and may result in additional plant or site specific preventive measures to ensure secur...

Отзывы: