Document No. 570-136
Installation Instructions
October 26, 2016
Page 4 of 11
Siemens Industry, Inc.
CAUTION
It is important that the neutral that
supplies the TEC must be earth
grounded at the source of the 24
Vac power.
Possible erratic equipment
operation or damage if neutral is not
grounded.
ATTENTION
Il est très important que le neutre
qui alimente le TEC soit mis à la
terre à la source de l’alimentation
24 Vca.
Risque de fonctionnement
incohérent de l’équipement ou de
dégats si le neutre n’est pas mis à
la terre.
10. For a Fast Acting Lab Electronic Actuator,
verify that the switches are set as shown in
Figure
Switch Settings for the Fast Acting
Lab Electronic Actuator
.
Damper
Venturi Air Valve
Switch Settings for the Fast Acting Lab Electronic
Actuator.
The installation is complete.
Dimensions.
Smoke Control Compliance
The following instructions and information apply if
used for smoke control sequence.
1. Install Smoke Control Listed products, enclosure
and transformer. See the
Product Numbers
and
Accessories
sections for more information.
2. Input Rating:
– 24V 60 Hz 60 VA maximum
3. Digital Output (DO) are the only I/O authorized
for smoke control applications.
Digital Output (DO) Electrical Ratings:
– 5 VA per DO/ maximum 40 VA total
4. The room temperature sensor (RTS) is installed
in the same area as the TEC.
5. Connection from the TEC to the field panel is a
maximum 4000 feet, 24 AWG minimum.
6. Wiring Range:
– Transformer: primary 14 AWG
– 24 Vac Input Power: 14 to 18 AWG
– DO: AI: 18 to 20 AWG
– DI: 18 AWG
– LAN: 20 to 24 AWG
– RST: 24 AWG
All circuits are power limited; FLN is RS-485,
RTS is RS-232. Digital Inputs (DI) are dry
contacts.
See the following documents for more
information on configuring smoke control
applications:
Smoke Control Systems Application and
Engineering Manual (
125-1806)
Smoke Control System Application Guide
(
125-1816)
NFPA and UL Standards Relevant to Smoke
Control System Application Guide (
125-
1817)