background image

Document No. 570-136 

Installation Instructions  

October 26, 2016 

Siemens Industry, Inc. 

Page 3 of 11 

Required Tools and Equipment 

  Small flat blade screwdriver 

  3/8-inch open end wrench 

  Needle nose pliers 

  1/4-inch poly tubing 

Prerequisites 

  Wiring conforms to NEC and local codes and 

regulations. For further information see the 

Wiring Guidelines Manual

  24 Vac Class II power available. 

  Supply power to the unit is OFF. 

  Any application specific hardware or devices 

installed. 

  Fume Hood Controller Enclosure is mounted and 

wiring has been roughed-in. 

  Operator Display Panel is installed and cable 

pulled to location of controller. 

Expected Installation Time 

30 minutes 

Installation Instructions 

 

NOTE: 

All wiring must conform to national and 

local codes and regulations (NEC, CE, 

etc.). 

1.  Secure the mounting rail in the controller’s 

desired location. 

2.  Place the ESD wrist strap on your wrist and 

attach it to a good earth ground. 

3.  Remove the controller from the static proof bag 

and snap it into place on the mounting rail. 

4.  If the controller will be used with a field panel, 

disconnect the field level network (FLN) trunk 

from the field panel. 

5.  Wire the FLN trunk to the controller. After all 

controllers are connected to the FLN, reconnect 
the FLN trunk to the field panel. 

 

6.  If the controller requires Offboard Air Modules, 

install them now following the appropriate 

Installation Instructions (see 

Product Numbers

). 

7.  Connect the point wiring (see 

Wiring Diagram

s). 

 

 

CAUTION 

DO Wiring – Each DO provides a 

Normally Open (NO) terminal and a 

Common (C) terminal. 
To reduce noise and the potential 

for ground loops, both connections 

of a 24 Vac load must be wired 

directly to the DO terminal on the 

controller board. 

 

 

8.  Plug the operator display cable into the ODP 

port. 

9.  Connect the power trunk. DO NOT apply 

power to the controller without first consulting 

the specialist. 

 

 

 

 

Содержание 570-00701PKA

Страница 1: ...nturi Air Valve to maintain control of a chemical fume hood with up to 2 sashes It uses fast acting electronic actuators shipped separately to control the exhaust control device WARNING The application cannot detect a broken wire to the analog input for the second sash An external sash aggregating device should be used to calculate the face area for all fume hoods with more than one sash This cont...

Страница 2: ...ne décharge électrostatique peut endommager la carte équipée Accessories Room Sensor Cable 25 ft Room Sensor Cable 50 ft 588 100A 588 100B Vertical Sash Sensor 50 inch range 80 inch range 546 04000 546 04001 Parts for Smoke Control Compliance Smoke Control Listed Large Equipment Controller Enclosure Long board and ATEC controllers 550 002K UL Listed Class 2 transformer with 120 240 277 480 Vac 50 ...

Страница 3: ...esired location 2 Place the ESD wrist strap on your wrist and attach it to a good earth ground 3 Remove the controller from the static proof bag and snap it into place on the mounting rail 4 If the controller will be used with a field panel disconnect the field level network FLN trunk from the field panel 5 Wire the FLN trunk to the controller After all controllers are connected to the FLN reconne...

Страница 4: ... and information apply if used for smoke control sequence 1 Install Smoke Control Listed products enclosure and transformer See the Product Numbers and Accessories sections for more information 2 Input Rating 24V 60 Hz 60 VA maximum 3 Digital Output DO are the only I O authorized for smoke control applications Digital Output DO Electrical Ratings 5 VA per DO maximum 40 VA total 4 The room temperat...

Страница 5: ...ful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient or relocate the receivin...

Страница 6: ...re to the analog input for the second sash An external sash aggregating device should be used to calculate the face area for all fume hoods with more than one sash AVERTISSMENT L application ne peut pas détecter un fil rompu allant à une entrée analogique pour le second châssis Un dispositif externe de cumulation de châssis devrait être utilisé pour calculer la surface à l entrée de toutes les hot...

Страница 7: ...en wiring any actuator that uses a 0 to 10V control signal and ties AC neutral to DC common an additional wire must connect the actuator AC neutral to the DC common of the PTEC TEC AO being used to control the actuator 24 Vac Modulating Control Actuator Symbol TEC Connection Function Terminal Connection Standard Color 1 H Supply SP G Red 2 C Neutral SN G0 Black 8 AO3 15 0 to 10V input signal Y Gra...

Страница 8: ...Document No 570 136 Installation Instructions October 26 2016 Page 8 of 11 Siemens Industry Inc Application 6740 Wiring Diagram ...

Страница 9: ...Document No 570 136 Installation Instructions October 26 2016 Siemens Industry Inc Page 9 of 11 Application 6741 Wiring Diagram ...

Страница 10: ...Document No 570 136 Installation Instructions October 26 2016 Page 10 of 11 Siemens Industry Inc Application 6742 Wiring Diagram ...

Страница 11: ...curity management and physical security systems The security functions on these products solutions and services are important components of a comprehensive security concept Drafting implementing and managing a comprehensive and up to date security concept customized to individual needs is nevertheless necessary and may result in additional plant or site specific preventive measures to ensure secur...

Отзывы: