background image

3ZX1012-0NJ61-2AN1

19

Unlocking the switching 
device flap

Maintenance

Check regularly that the ventilation slots in the front covers of the switching devices are free 
of dirt and clean them if necessary at suitable intervals.

Fitting the in-line fuse 
switch-disconnectors

If the cubicle has been designed for in-line switching devices of plug-in type without shock-
hazard protection in front of the cubicle busbar, the cubicle busbar (relevant busbar section) 
must be isolated before a in-line fuse switch-disconnector is fitted or removed.

Unlocking the switching device 
flap by blade in position "I":
Attach the tool at a position of 90° 
vertical to the cover and push it 
into the notch until resistance is 
felt. Then depress the tool until 
the flap interlock is deactivated 
(see Fig.).

Do not leave the switching 
device unattended with the 
cover open!

Before closing the cover return the lever to the "I" position (lever points in the direction of the 
cover lock).
Then swivel the cover onto the switching device until the interlock mechanism reengages, 
and close the lock of the cover.

Caution

Touching live parts results in death or severe personal 
injury.

Only qualified personnel may operate the switchgear; they 
must be familiar with the instructions and follow the warning 
notices.

Always make sure that the breaker is in the OFF position 
before fitting or removing the strips!

Step

Procedure

1

The strips are pushed into the cubicle until the guide pins (sharp pins at the 
rear, left an right, of the switching device) engage in the sectional holes of the 
left and right-hand distribution bus side walls and the contacts have been 
pushed directly onto the busbars.
Ensure that the switching device is in a horizontal position when pushing in the 
strips.

2

The strips are then fastened on 
the left and right- hand sides to 
the vertical front sections with 
the aid of two screws M6X12. 
No special tool is required if on 
the right-hand side the ammeter 
and/or the monitoring indicator 
are pulled out beyond the front. 
A ratchet with short insert faci-
litates tightening of the screws 
(see Fig.).

Содержание 3NJ6 Series

Страница 1: ...1 1AN1 3NJ6120 Bestell Nr 3ZX1012 0NJ62 1AN1 3NJ6140 Bestell Nr 3ZX1012 0NJ64 1AN1 3NJ6160 Bestell Nr 3ZX1012 0NJ64 1AN1 3NJ6913 Bestell Nr 3ZX1012 0NJ63 1AN1 Frontansicht Bild 1 Fontansicht mit gesteckten Leisten und teilweise entfernten Geräten mit Blick auf Steckschienen Geräte für den Hilfs stromkreis Direkt im Schaltgerät ist Platz für ein Amperemeter 48 X 48 siehe Bild 1 WARNUNG Gefährliche ...

Страница 2: ...en d Lasttrennschalter mit unabhängigem handbetätigten Sprungantrieb Anschlussquerschnitte Folgende Tabelle gibt die Anschlussquerschnitte für den Anschluss mit Kabelschuh und Kabel klemme an Die Hilfsschalteranschlüsse der steckbaren Sicherungsleiste lie gen im rechten hinteren Gerätebe reich und sind vom Kabel anschlussraum zugängig siehe Bild Der Anschluss erfolgt mit Flachstecker 6 3 X 0 8 mm ...

Страница 3: ...tor förmigen Kabels Bild 4 Positionierung eines sektorförmigen Kabels in der Klemme Kabelanschluss abhän gig von Gerätegröße und Anschlussart Werkzeug Klemmenschlüssel Bestell Nr 3NJ6916 4CA00 Die Kabel können an alle Lasttrennleisten sowohl mit Kabelschuh als auch direkt über Kabel klemmen angeschlossen werden Die folgenden Darstellungen zeigen den Anschluss bei den einzelnen Baugrößen Bild 5 Bau...

Страница 4: ...n klappen entriegeln Aufheben der Front klappenverriegelung Die dünnere Griffleiste bis zum Anschlag in Richtung Griff ziehen und damit das Gelenk im Schalt hebel freigeben Danach den Griff nach rechts vor den Gerätedeckel schwenken GEFAHR Teile des Hauptstromkreises sind unter Spannung Den Gerätedeckel in dieser Einschubstellung sollte nur wenn erforderlich z B Messung von qualifiziertem Personal...

Страница 5: ...der Verriegelungsmechanismus selbsttätig wieder einrastet und den Verschluss schließen WARNUNG Das Berühren der spannungsführenden Teile führt zum Tode oder hat schwere Körperverletzungen zur Folge Die Anlage darf nur von qualifiziertem Personal betrieben wer den das mit der Anleitung vertraut ist und insbesondere die Warnhinweise beachtet Die Leisten nur in ausgeschalteter Stellung montieren bzw ...

Страница 6: ...rs lösen Für die rechte Seite sind ggf A Meter und oder Sicherungsüberwachungsanzeige vor die Front zu ziehen Eine Ratsche mit kurzem Einsatz erleichtert das Lösen der Schrauben Schritt Vorgehenweise 1 Gerätedeckel schließen und sichern 2 Schaltgriffausklappen und mit der linken Hand umfassen 3 Nun die Fingerspitzen der rechten Hand seit lich in der Aussparung des Gerätedeckels rechts neben dem Ve...

Страница 7: ...Deckel in Verschlussnähe gegenhalten 2 Das Werkzeug zum Herausziehen des Gerätes Bestell Nr 3NJ6916 4BA00 links im Scharnierteil des Gerätedeckels oben und unten einhängen Blick auf ein Scharnier des Gerätedeckels 3 Durch leichtes Ziehen den sicheren Sitz des Werkzeugs prüfen Dann das Werkzeug mit beiden Händen an der Griffstange fassen und das Gerät mit etwas Schwung von den Kontakten zie hen Nun...

Страница 8: ...ACHTUNG Für die Planung eines Einbaus bei Baugröße 00 Geräte mit Klemmenanschluß vorsehen Für Nachrüsten bei Anschluss mit Kabelschuhen darauf achten dass das Kabel ggf nachzu setzen und der Kabelschuh nach Durchführen des Leiters durch den Wandler aufzupressen ist Lage des Messwandlers Die Standard Kabelabdeckungen sind nur für die in Bild 13 15 und 17 gezeigten 1 phasigen Messungen einsetzbar Bi...

Страница 9: ...3ZX1012 0NJ61 2AN1 9 Bild 17 Baugröße 2 und 3 Lage des Bild 18 Baugröße 2 und 3 Lage des Messwandlers 1 phasig Messwandlers 3 phasig L3 L2 L2 L3 L1 L1 L1 L1 ...

Страница 10: ...5 590 10 Loch für Befestigungs schraube 590 49 590 99 590 198 24 5 8 49 33 Steckkontakt Führungs stift 49 21 21 49 21 21 33 3NJ6110 Baugröße 00 3NJ6120 Baugröße 1 3NJ6140 und 3NJ6160 Baugrößen 2 und 3 89 27 69 25 100 33 max 230 3NJ6913 1AA00 Baugröße 00 3NJ6913 2BA00 Baugröße 1 3NJ6913 1CA00 Baugrößen 2 und 3 ...

Страница 11: ...3ZX1012 0NJ61 2AN1 11 Maßbilder 4 polig 550 525 185 185 77 5 12 5 10 97 5 L1 L2 L3 N 590 99 590 149 249 590 24 5 8 57 49 33 82 113 49 21 21 33 200 40 11 Baugröße 00 Baugröße 1 Baugrößen 2 und 3 ...

Страница 12: ...längerungen 3NJ6911 3AA00 Baugröße 00 Kabelanschlüsse Baugröße 00 3NJ6911 3BA00 Baugröße 1 3NJ6911 3CA00 Baugrößen 2 und 3 200 525 77 5 542 185 185 48 198 48 83 5 36 64 43 22 24 5 81 127 mit Kabelklemmenanschluß für Stehbolzenanschluß ...

Страница 13: ...mit Kabelklemmenanschluß für Stehbolzenanschluß Technische Änderungen vorbehalten Subject to change without prior notice Siemens AG 2000 Bestell Nr Order No 3ZX1012 0NJ61 2AN1 Technical Support Tel 49 0 9131 7 43833 8 17 MEZ Fax 49 0 9131 7 42899 E mail NST technical support erl7 siemens de Internet www ad siemens de support ...

Страница 14: ... Order No 3ZX1012 0NJ61 1AN1 3NJ6120 Order No 3ZX1012 0NJ62 1AN1 3NJ6140 Order No 3ZX1012 0NJ64 1AN1 3NJ6160 Order No 3ZX1012 0NJ64 1AN1 3NJ6913 Order No 3ZX1012 0NJ63 1AN1 Front view Fig 1 Front view with plugged on in line devices and some devices removed showing plug on buses with front cover Equipment for the auxi liary circuit There is room for a 48 x 48 ammeter directly in the switching devi...

Страница 15: ...operated snap action mechanism Cross sections The following table contains the possible cross sections for connection with cable lugs and cable terminals Auxiliary switch terminals of the plug on in line type fuse switches are located in the right hand rear area for the switching device and are accessi ble from the cable connection department see Fig Auxiliaries are connected with flat pin plug 6 ...

Страница 16: ... of size 00 Connection of a sector shaped cable Fig 4 Positioning a sector shaped cable in the terminal Cable connection depen ding on switching device size and type of connec tion Tool Terminal wrench Order No 3NJ6916 4CA00 All in line fuse switch disconnectors can be connected to the cables either with cable lug or directly via cable terminals Fig 5 Size 00 view of 3 terminals 1 cable connected ...

Страница 17: ...ling the front flap interlock Pull the slim grip outwards as far as it will go so as to free the joint in the operating lever Then swing the grip to the right in front of the cover of the unit Danger Parts of the main circuit are live Only authorized and qualified personnel may open the compartment door in this position of the withdrawable unit and only if necessary e g for measuring purposes Fuse...

Страница 18: ...f the cover lock Then swivel the cover onto the switching device until the interlock mechanism reengages and close the lock of the cover Caution Touching live parts results in death or severe personal injury Only qualified personnel may operate the switchgear they must be familiar with the instructions and follow the warning notices Always make sure that the breaker is in the OFF position before f...

Страница 19: ... For the right hand side the ammeter and or fuse monitoring indicator may have to be pulled out beyond the front A ratchet with short Torx insert facilitates undoing of the screws Step Procedure 1 Close and secure front flap 2 Swing out the handle and grasp it with the left hand 3 Now insert the finger tips of your right hand in the lateral cutout of the switching device cover on the right near th...

Страница 20: ...s to apply counterforce see Fig 2 Attach the tool for removing the device order no 3NJ6916 4BA00 on the left hand side in the hinge at the top and bottom and engage it View of switching device cover hinge 3 Check that the tool is firmly in place by pul ling on it gently Then grasp the tool with both hands and pull the device smartly away from the con tacts Now place one hand under the device ans p...

Страница 21: ...ize 00 switching devices should be provided with terminals When retrofitting onto cable lug connections the cable may need to be repositioned and the cable lug pressed open after the lead has been passed through the current transformer Position of the measuring current transformers The standard cable covers may only be used for the single phase measurements illustrated in Figs 13 15 and 17 Fig 13 ...

Страница 22: ...3ZX1012 0NJ61 2AN1 23 Fig 17 Sizes 2 and 3 position af 1 phase Fig 18 Sizes 2 and 3 position of 3 phase measuring current transformer measuring current transformer L3 L2 L2 L3 L1 L1 L1 L1 ...

Страница 23: ...9 33 Plug type contact Guide pin 49 21 21 49 21 21 33 550 525 185 185 206 18 90 12 5 121 200 30 35 590 10 Hole for mounting srew 3NJ6110 size 00 3NJ6120 size 1 3NJ6140 and 3NJ6160 sizes 2 and 3 89 27 69 25 100 33 max 230 3NJ6913 1AA00 size 00 3NJ6913 2BA00 size 1 3NJ6913 2CA00 sizes 2 and 3 ...

Страница 24: ...3ZX1012 0NJ61 2AN1 25 Dimension drawings 4 pole 550 525 185 185 77 5 12 5 10 97 5 L1 L2 L3 N 590 99 590 149 249 590 24 5 8 57 49 33 82 113 49 21 21 33 200 40 11 Size 00 Size 1 Sizes 2 und 3 ...

Страница 25: ...ontact extensions 3NJ6911 3AA00 size 00 Cable connections Size 00 3NJ6911 3BA00 size 1 3NJ6911 3CA00 sizes 2 und 3 200 525 77 5 542 185 185 48 198 48 83 5 36 64 43 22 24 5 81 127 With cable clamp connection For stud terminal ...

Страница 26: ...cable clamp connection For stud terminal Technische Änderungen vorbehalten Subject to change without prior notice Siemens AG 2000 Bestell Nr Order No 3ZX1012 0NJ61 2AN1 Technical Support Tel 49 0 9131 7 43833 8 17 MEZ Fax 49 0 9131 7 42899 E mail NST technical support erl7 siemens de Internet www ad siemens de support ...

Отзывы: