Configuration
4.6 Examples/applications
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
69
When the EMERGENCY-STOP is actuated, the motor starters' control supply voltage is shut
down and the motor is isolated from the power supply. Due to the internal self-monitoring of
the 3RM11/13 Failsafe motor starters in compliance with SILCL 3/PL e, there is no need for
a feedback signal to the 3SK1 safety relay.
DANGER
Hazardous Voltage.
Can Cause Death, Serious Injury, or Property Damage.
Possible failure of the safety function
When operating with the 3SK1 safety relay and a device connector, the supply voltage for
3RM11/3RM13 Failsafe motor starters is established via the device connectors.
In this case, do not connect anything to terminals A1 and A2 of the 3RM11/3RM13 Failsafe
motor starters, in order to prevent bypassing of the safety function.
WARNING
Failure of the safety function
Hybrid operation of 3RM10/3RM12 Standard motor starters with 3RM11/3RM13 Failsafe
motor starters in safety-related applications is not admissible.
Only ever use safety-related motor starters (3RM11 Failsafe and 3RM13 Failsafe) in safety-
related applications.
Note
Please observe the information about the control supply voltage and the control inputs in the
Chapters "Device versions (Page 24)" and "Control circuit (Page 117)".