107
Fault
LED
Fault
signaling
output
Reaction of
feedback
circuit
Possible cause/corrective measure
DEVICE FAILURE
STATE
RESET
MODE
Yellow
Red
Off
Green/off* Active
-
•
Overload trip motor protection
•
Motor blocks during starting or operation
Flashing
yellow
Red
Off
Green/off* Active
-
•
No current flow despite ON command:
Check whether the connected load
fulfills the minimum current (Page 57).
•
Phase failure: Check whether all three
phases are applied.
Flashing
red
Red
Off
Green/off* Active
Active
Malfunction: For information about
correcting faults, please refer to the section
"Fault rectification (Page 108)".
* = depending on the selected RESET MODE
Note
Difference between Standard and Failsafe
3RM11 Failsafe and 3RM13 Failsafe motor starters signal a phase failure immediately.
3RM10 and 3RM12 Standard motor starters signal a phase failure after 5 s.
Test
LED
Fault
signaling
output
Reaction of
feedback
circuit
Device status / operating mode
DEVICE FAILURE
STATE
RESET
MODE
Yellow
Red
Green
Green
Self-test: Indicator test
2 s
Flickering
red
Current flow test: Current not
flowing
3 s
Flashing
red
Current flow test: Current
flowing
Flashing
yellow
Red
Off
Off
Active
Self-test: Overload tripping
>5 s
Flashing
red
Red
Off
Off
Active
Active
Overload trip failed