Technical data
9.1 Motor starters
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
117
9.1.3
Control circuit
The technical data of the control circuit depends on the control supply voltage.
Rated control supply voltage
Order number
24 V DC
3RM1...-.AA0.
110 ... 230 V AC/110 V DC
3RM1...-.AA1.
A distinction is made in the two tables between the 3RM10/3RM12 Standard motor starters
and the 3RM11/3RM13 Failsafe motor starters.
3RM10/3RM12 Standard motor starters
3RM10..-.AA0. 3RM12..-.AA0. 3RM10..-.AA1. 3RM12..-.AA1.
Type of voltage
DC
AC/DC
Control supply voltage 1
•
at 50 Hz for AC
V
-
110 … 230
•
at 60 Hz for AC
V
-
110 … 230
•
for DC
V
24
110
Control supply voltage frequency
Hz
-
50 / 60
Operating range factor control supply
voltage rated value
•
for DC
0.8 … 1.25
0.85 … 1.1
•
at 50 Hz for AC
-
0.85 … 1.1
Control current
A
0.07
0.02
Input voltage at the digital input
for DC
V
24
110
Input voltage at the digital input
with AC
V
-
110 … 230
Input voltage at the digital input
•
with signal <1>
–
for DC
V
15 … 30
79 … 121
–
with AC
V
-
93 … 253
•
with signal <0>
–
with AC
V
-
0 … 40
–
for DC
V
0 … 5
0 … 40
Input current at the digital input
•
for signal <1>
mA 11
2
•
with signal <0>
mA 1
0.4
Содержание 340
Страница 2: ......
Страница 16: ...Introduction 1 9 Correction sheet SIRIUS 3RM1 motor starter 16 Manual 11 2013 A5E0345285095020A RS AB 002 ...
Страница 164: ...Correction sheet SIRIUS 3RM1 motor starter 164 Manual 11 2013 A5E0345285095020A RS AB 002 ...
Страница 172: ...Index SIRIUS 3RM1 motor starter 172 Manual 11 2013 A5E0345285095020A RS AB 002 ...
Страница 173: ......