Configuration
If the device on the SDL connection needs data from the bus node or from the FPLC, but
the bus node has not yet been finally configured, the device can report an error on the
SDL connection. If necessary, you should give priority to configuring the bus node or pro-
gramming the FPLC in order to test the configuration of the device on the SDL connec-
tion.
The UE4155 bus node monitors the configuration of the devices on the SDL connection.
If you reconfigure or exchange this, then you should …
– modify the configuration of the bus node, if necessary, and
– at least transfer the configuration to the bus node once more.
In the event of an error message from a device on the SDL connection, always also read
the diagnostics data of the bus node. This will provide additional information for resolving
the error.
8.6
Setting the PROFIsafe address
In order for you to operate the bus node as a PROFIsafe user, this must have a PROFIsafe
address. The PROFIsafe address must correspond to the appropriate setting in the FPLC
hardware-configuration program.
You can set the PROFIsafe address in the bus node as follows:
Start the hardware-configuration program.
In the PROFIBUS configuration of the bus node, read the value of parameter
F_Dest_Add
Transfer the value you have read as the PROFIsafe address to the bus-node configura-
tion with the aid of the CDS.
Device symbol
UE4100 PROFIsafe
, context menu
Configuration draft
,
Edit
, file card
General
, option
PROFIsafe address (F_Dest_Add)
.
8.7
Configuration of the bus-node inputs and outputs
Configure the field-signal and SDL connections as planned with the aid of the CDS.
Chapter 3.5 “Configurable functions” on page 16 as well as the online help on the CDS
contain detailed information on the interaction of the individual settings.
Device symbol
UE4100 PROFIsafe
, context menu
Configuration draft
,
Edit
, file card
I/O
of the corresponding field-signal connection.
Transfer the configuration to the bus node as described in the CDS online help.
If necessary, remove the connector from the configuration connection when you have
concluded the configuration.
Screw the device’s protection cap back onto the device after you have finished
configuring it. The bus node will otherwise no longer comply with enclosure rating.