6
Electrical installation
6.1
Wiring instructions
NOTE
Pre-assembled cables can be found online at:
•
NOTICE
Faults during operation and device or system defects!
Incorrect wiring may result in operational faults and defects.
■
Follow the wiring notes precisely.
The enclosure rating stated in the technical data is achieved only with a screwed plug
connector or protective cap.
Connect the connecting cables in a de-energized state. Do not switch on the supply
voltage until installation is complete and all connecting cables are connected to the
device and control.
The supply voltage must be as specified in the technical data,
.
When commissioning, protect the device from moisture and contamination.
6.2
Prerequisites for safe operation of the device
WARNING
Risk of injury and damage caused by electrical current!
As a result of equipotential bonding currents between the device and other grounded
devices in the system, faulty grounding of the device can give rise to the following
dangers and faults:
•
Dangerous voltages are applied to the metal housings.
•
Devices will behave incorrectly or be destroyed.
•
Cable shielding will be damaged by overheating and cause cable fires.
Remedial measures
•
Only skilled electricians should be permitted to carry out work on the electrical
system.
•
If the cable insulation is damaged, disconnect the voltage supply immediately and
have the damage repaired.
•
Ensure that the ground potential is the same at all grounding points.
•
Where local conditions do not meet the requirements for a safe earthing method,
take appropriate measures. For example, ensure low-impedance and current-carry‐
ing equipotential bonding.
The device is connected to the peripheral devices (any local trigger sensor(s), system
controller) via shielded cables. The cable shield – for the data cable, for example –
rests against the metal housing of the device.
The device can be grounded through the cable shield or through a blind tapped hole in
the housing, for example.
6
ELECTRICAL INSTALLATION
16
O P E R A T I N G I N S T R U C T I O N S | UC12
8010984/1BNB/2022-05-12 | SICK
Subject to change without notice