Connecting cables
Requirements for the connecting cables
Table 22: Requirements for the connecting cables
Parameter
Value
Min. wire cross-section
0.25 mm²
R max.
60 Ohm/km
C max.
120 nF/km
L max.
0.65 mH/km
Recommended cable type = LIYY 8 x 0.25 mm² or 5 x 0.34 mm²
Maximum cable lengths
Table 23: Maximum cable lengths
Max. number of safety lock‐
ing devices
Possible output current per
OSSD (mA)
Max. length of cable from the
last safety locking device to
the controller (m)
5
10
150
25
100
50
80
100
50
150
25
6
10
120
25
90
50
70
100
50
150
25
10
10
70
25
60
50
50
100
40
150
25