Test pulse width
Depends on the configured sensor type
Length of cable (single)
≤ 100 m
Cable resistance
≤ 10 Ω
Table 11: Test pulse interval, test pulse width, and max. test pulse delay depending on the
configured sensor type
Sensor type
Test pulse interval
Test pulse width
Max. test pulse delay
EMSS
40 ms
2 ms
–
CMSS
40 ms
2 ms
–
OSSD
–
–
–
Fast SCSD
40 ms
8 ms
12 ms
Slow SCSD
400 ms
58 ms
12 ms
SMAT
40 ms
18 ms
–
Table 12: Electrical data – Application diagnostic output (Y1, Y2)
Type of output
Push-pull semiconductor output, short-circuit
protected
Output voltage HIGH:
(U
V
– 3 V) … U
V
Output voltage LOW:
0 V … 3 V
Input current (NPN)
≤ 15 mA
Output current (PNP)
≤ 120 mA
Table 13: Electrical data - enabling current paths (13, 14, 23, 24, 33, 34)
Minimum switch-off time
1)
150 ms
Number of enabling current paths (normally
open, safe)
3
Contact type
Positively guided
Contact material
Silver alloy, gold flash plated
Switching voltage
At altitudes below 2,000 m above sea level
10 V DC … 250 V DC
10 V AC … 250 V AC
At altitudes 2,000 m above sea level …
4,000 m above sea level
10 V DC … 150 V DC
10 V AC … 150 V AC
Switching current
10 mA … 6 A,
Sum current
≤ 12 A
Utilization category
AC-15: 230 V, 5 A (IEC 60947-5-1)
DC-13 (0.1 Hz): 24 V, 4 A (IEC 60947-5-1)
DC switching capacity
0.1 W … 200 W,
AC switching capacity
0.1 VA … 1,500 VA
Switching frequency
≤ 1 Hz
Mechanical service life
10 × 10
6
switching operations
Contact fuse with safety fuse gG or circuit
breaker C
Max. 6 A
Max. short-circuit protection
≤ 400 A
Rated insulation voltage
At altitudes up to 2,000 m above sea level
250 V AC
11
TECHNICAL DATA
30
O P E R A T I N G I N S T R U C T I O N S | ReLy MULT1
8024307/2021-07-30 | SICK