© SICK AG • Presence Detection • Subject to change without notice • 8018665.10RD 33
Operating instructions IO-Link Master IOLG2PN-03208R01 – PROFINET
Diagnostics
Designation
Bit
Description
Possible values
Description
Submodule
Diagnostic State
13
Submodule diagnostics
0x00
No other submodule diagnostics
present
0x01
At least one other diagnostic of
the submodule available
Reserved
14
–
–
–
AR Diagnostic State 15
Module diagnostics
0x00
No further diagnostics of the
module available
0x01
At least one other diagnostic of
the module available
User Structure Ident
2 bytes, describes the type of
diagnostics
0x8000
Channel specific diagnostics
Table 18: AlarmSpecifier
Channel Number
2 bytes of data, which describe where the error occurred on the module.
Possible values
Bit
Value
Position
0 to 3
0x00
Port 0 Pin 4
0x01
Port 1 Pin 4
0x02
Port 2 Pin 4
0x03
Port 3 Pin 4
0x04
Port 4 Pin 4
0x05
Port 5 Pin 4
0x06
Port 6 Pin 4
0x07
Port 7 Pin 4
0x08
Port 0 Pin 2
0x09
Port 1 Pin 2
0x0A
Port 2 Pin 2
0x0B
Port 3 Pin 2
0x0C
Port 4 Pin 2
0x0D
Port 5 Pin 2
0x0E
Port 6 Pin 2
0x0F
Port 7 Pin 2
Definitions of error cases
Bit 4
0
Error on a port of the IO-Link Master
1
Error on an IO-Link device
Bit 0 to 3 indicate which port the defective device
is connected to.
2
Error on IO-Link Master
In this case bits 0 to 3 have no significance, since
the error affects the entire IO-Link Master, as for
example “with undervoltage”.
Table 19: Channel Number