Operating instructions IO-Link Master IOLG2PN-03208R01 – PROFINET
Electrical connection
16
© SICK AG • Presence Detection • Subject to change without notice • 8018665.10RD
Excessive current load
ATTENTION!
Equipment damage due to excessive current load!
An excessive current load may result in damage to the
equipment.
• Do not exceed the maximum permissible total current
of 8 A for the IO-Link Master.
• Each output provides a maximum current of 2 A.
• The sensors/bus and the actuator should be powered
via separate current sources if possible.
Incorrect grounding
ATTENTION!
Incorrect grounding!
An incorrect grounding may result in equipment damage
or malfunction.
• The grounding between the IO-Link Master and the
machine must be a low-impedance system.
• The ground connection must be as short as possible.
5.2
IO-Link Master electrical connection
1. Ensure power supply is not connected.
2. Connect the IO-Link Master to the functional grounding of the system
using the supplied ground strap. See the figure below.
3. Connect supply voltage to “POWER IN” using a suitable cable.
4. Make fieldbus connection via PROFINET port 1/PROFINET port 2.
5. Connect IO-Link devices or standard devices to the IO-Link ports.
6. If provided, connect the next gateway to “POWER OUT”.