Operating Instructions
Chapter
9
Flexi Classic Gateways
8011834/YT28/2016-03-15
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
97
Subject to change without notice
EtherNet/IP Gateway
Overview of the selection and entry fields:
Selection/entry
window
Factory
setting
Description
Rx (To PLC)
Transfer Mode
Polling
Determines the type of data transfer from
UE410
F
EN1 to the PLC.
Polling
— PLC requests the data.
Write-to-Tag/File
— UE410-EN1 writes the data to
the PLC memory.
Off
— PLC Interface disabled.
See
section
9.4.1
Tx (From PLC)
Transfer Mode
PLC Writes
Determines the type of data transfer from the PLC
to UE410-EN1.
PLC Writes
— PLC writes to the UE410-EN1
memory.
Read-from-Tag/file
— UE410-EN1 requests data
continuously from the PLC.
Off
— PLC Interface disabled.
See
section
9.4.2
Settings for the operating modes Write-to-Tag/File and/or Read-from-Tag/file:
PLC IP Address
0.0.0.0
Specifies the PLC address in standard format xxx.xxx.xxx.xxx.
The selected data sets are transferred to this IP Address.
PLC Controller Slot
Number
0
Specifies the PLC slot number of the controller (typically 0).
Settings for the operating mode Write-to-Tag/File:
Maximum PLC
Update Rate
40
Defines the maximum rate (the minimum time interval) for
sending the data sets to the PLC. Settings occur dependent on
the PLC processing speed.
Minimum = 10 ms, maximum = 65535 ms. The default value of
40 ms is suitable for most PLCs.
Note
: If this value is greater than the Heartbeat Update Interval,
the Heartbeat Update Interval is increased (slowed down) to
this value.
Enable Heartbeat
Message
Deactivated
Activates updating of the active data sets with the set
Heartbeat Update Rate.
Note
: Either this option or Update Immediately on Status/Confi-
guration Change must be activated, otherwise no data will be
transferred!
Heartbeat Update
Interval
5000
Specifies the Heartbeat Update Interval in milliseconds with
which the data are updated in the PLC.
Standard = 5000 ms, Minimum = 10 ms, Maximum
= 65535 ms.
Note
: If the Maximum PLC Update Rate is larger than the
Heartbeat Update Rate, the Heartbeat Update Rate is in-
creased (slowed down) to this value.
Update
Immediately on
Status/Configu-
ration Change
Deactivated
Specifies whether the UE410-EN is to update the data in the
PLC immediately when changes occur in the data sets. If not
activated, the update is carried out with the next Heartbeat
Interval.
Note
: Either this option or Enable Heartbeat Message must be
activated, otherwise no data will be transferred!
Tab. 91: Configuration of the
interface to the PLC