Chapter
3
Operating Instructions
Flexi Classic Gateways
18
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
8011834/YT28/2016-03-15
Subject to change without notice
Flexi Classic gateways
O
P
, O
N
(only UE410-GU)
Communication for global
emergency stop to the previous or
next module
0 = Global emergency stop is
inactive
1 = Global emergency stop is
active
MUTE
Status bit for Muting
0 = Muting is inactive
1 = Muting is active
BYP
Status bit for Bypass
0 = Bypass is inactive
1 = Bypass is active
3.2.13
MKD1
Module configuration data 1: Position of the program switch/function switch/time range
(not UE410-GU)
Bit 7
6
5
4
3
2
1
Bit 0
SW1
SW2
SW1
Top switch setting 0-9
SW2
Bottom switch setting 0-9
3.2.14
MKD2
Module configuration data 2: (UE410-MU/XU configuration on S1, S2, S3)
(UE410-MM/XM: configuration on S1)
(not UE410-GU)
Bit 7
6
5
4
3
2
1
Bit 0
UE410-MU
UE410-XU
–
S3
S2
S1
UE410-MM
UE410-XM
–
–
–
S1
S1
Configuration jumper on S1
00 = Open
S2
Configuration jumper on S2
01 = On X1
10 = On X2
S3
Configuration jumper on S3
11 = Active at +U
B
Tab. 14: MKD1
Tab. 15: MKD2