Operating instructions
Chapter
11
Flexi Classic
8011509/YPP0/2015-10-26
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
97
Subject to change without notice
Technical specifications
Minimum
Typical
Maximum
Power-up delay
70 ms
–
–
Synchronous time monitoring
program 1, 2
–
1500 ms
–
Synchronous time monitoring
program 4 and 5
–
500 ms
–
Muting ON program 3
–
–
61 ms
Muting OFF program 3
–
61 ms
165 ms
Muting gap suppression
program 3
95 ms
–
100 ms
Reset time
–
–
124 ms
Teach-in time of ENTER button
UE410-MU (during power-up)
–
–
3 s
Duration of actuation of the reset
button (only S1, S2)
50 ms
–
5 s
Control outputs (X1, X2)
Number of outputs
–
–
2
Type of output
PNP semiconductors, short-circuit protected, cross-
circuit detecting
Output voltage
16 V DC
–
30 V DC
Output current
–
–
120 mA
Test period (X1, X2) program 1, 2,
4, 5, 6, 9
–
–
40 ms
Test period (X1, X2) program 3.2
–
–
X1 = 384 ms
X2 = 40 ms
Load capacity
–
–
1,000 nF
Cable resistance
–
–
100 Ω
Output circuit (Q1, Q2, Q3, Q4)
Number of outputs
–
4
–
Type of output
PNP semiconductors, short-circuit protected, cross-
circuit detecting
14)
Switching voltage
18.4 V DC
–
30 V DC
Switching current
I
Qn
, T
A
≤ 45 °C
–
–
2,0 A
I
Qn
, T
A
≤ 55 °C
–
–
1,6 A
11)
Time between muting condition valid (I3/I4 high) and muting possible.
12)
Max. switch-off time at muting error.
13)
One muting input (I3 or I4) may be LOW for the specified time.
14)
Cross circuit detecting only within a module.
15)
The total output current for a Flexi Classic system is limited. The current for supplying all sensors that are
connected to the UE410-MU/XU (X1/X2) and UE410-8DI (X1-X8) must be I < 600 mA and the current on a
Flexi Classic gateway must be I < 100 mA. If this total current is insufficient, please contact the SICK hotline.