Chapter
11
Operating instructions
Flexi Classic
104
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
8011509/YPP0/2015-10-26
Subject to change without notice
Technical specifications
Minimum
Typical
Maximum
Terminal and connection data
Single-wire or fine-wire
1 × 0.14 mm² to 2.5 mm² or
2 × 0.14 mm² to 0.75 mm²
Fine-wire with terminal crimps to
EN 46
228
1 × 0.25 mm² to 2.5 mm² or
2 × 0.25 mm² to 0.5 mm²
Insulation stripping length
–
–
8 mm
Maximum tightening torque
–
–
0.6 Nm
For UL 508 and CSA applications
UE410-xx
3
…, UE410-xxx
3
…
– Connection cross-section
AWG 30-12
(only use 60/75 °C copper flexible wire)
– Tightening torque
5-7 lb
⋅
in
UE410-xx
4
…, UE410-xxx
4
…
– Connection cross-section
AWG 30-12
(only use 60/75 °C copper flexible wire)
Safety specific characteristics
All these data are based on an ambient temperature of +40 °C.
Safety Integrity Level
SIL3 (IEC 61
508)
SIL claim limit
26)
SILCL3 (EN 62
061)
Category
Category 4 (EN ISO 13
849-1)
Performance Level
26)
PL e (EN ISO 13
849-1)
T
M
(mission time)
20 years (EN ISO 13
849-1)
PFD
2.1 × 10
–5
PFHd (1/h)
6.0 × 10
–9
SFF
96
%
DC
99
%
Single-channel input,
single-channel output
Dual-channel input,
single-channel output
PFD (
⊕
)
2.2 × 10
–5
2.1 × 10
–5
% of SIL3
2.2
%
2.1
%
PFHd (1/h)
6.0 × 10
–9
6.0 × 10
–9
% of SIL3
6.0
%
6.0
%
26)
For detailed information on the safety design of your machine/system, please contact your local SICK
subsidiary.
Tab. 42: PFD and PFHd
values for UE410-GU