4
PROJECT PLANNING
18
8017621/ZPQ5/2017-08-15|SICK
S U P P L E M E N T A R Y O P E R A T I N G I N S T R U C T I O N S | AOS502 STS
Subject to change without notice
4.2.3
Size and position of the test fields
The system’s self-monitoring test fields are typically aligned with a suitable flat object
on the crane or directly with a flat area of the crane body. In the figure below, one of the
crane girders is used as the test target.
Fig. 10: Crane leg as test target
The test fields are pre-defined. They are formed as triangles and must be adapted to the
existing conditions on-site.
Fig. 11: Size and position of the test fields
By default, the test fields are pre-defined with the following dimensions in SOPAS:
Monitoring field
Length
Width at maximum length
Scan angle
Test field right/left
35 m
4 m
7° symmetrical
Tab. 4: Field sizes for the test fields