Commissioning
Operating Instructions
Chapter
4
21
8014012/1EF3/2021-12-08
Subject to change without notice
© SICK AG
•
Germany
•
All rights reserved
A3M60 Basic
Fig. 9: Preset step 1
Fig. 10: Preset step 2
Fig. 11: Preset step 3
WARNING
4.4.5
Checking preset value
If you transmit a preset value to the A3M60 Basic, then in the
Monitor/Modify Variables
dialog box for the STEP7 you can see the PEW (peripheral input word) and PAW (peripheral
output word).
00000024h is transmitted from the encoder to the PLC as the position.
00000010h is transmitted from the PLC to the encoder as the preset.
Bit 31 is set to 0, as a result the preset value is not applied.
80000010h is transmitted from the PLC to the encoder as the preset.
Bit 31 is set to 1, i.e. a transition from 0 to 1 occurs, the preset value 10h is applied.
00000010h is transmitted from the encoder to the PLC as the position.
4.5
Test notes
Commissioning requires a thorough check by authorized personnel!
Before you operate a system equipped with the A3M60 Basic for the first time, make sure
that the system is first checked and released by authorized personnel. Please read the
notes in chapter 2
on page 7.