EAAM057608EN      

 

 

 

                      GC250 Technical Manual    63 

 

For  three-phase  systems,  the  phase-to-phase  voltages  are  displayed;  for  the  one-phase 
systems, the phase-to-neutral voltage and the voltage between neutral and negative battery 
are displayed and the rotation direction is not displayed. 

To the bottom right there is an icon that allows immediate identification of the fact that the page 
is related to the GENERATOR measures. 

 

7.4.7.5

 

M.05 GENERATOR 

This page is only shown for the three-phase systems and only if the system is configured to 
use the neutral connection (see par.  5.10.1In fact, every digital  input can  have  an AND/OR 
logic associated,  which  determines its status (see par.  ). The three phase-neutral  voltages 
are shown and the negative of the battery, in addition to the rotation direction of the phases 
(clockwise or counter clockwise).  

To the bottom right there is an icon that allows immediate identification of the fact that the page 
is related to the GENERATOR measures. 

 

7.4.7.6

 

M.06 CURRENTS 

This window displays the phase currents (three or only one for single-phase systems)) of the 
Generator measured by the controller board.  

 

7.4.7.7

 

M.07 POWERS 1 

The active powers and power factors are shown, total and phase by phase (dashes only for 
phase  2  and  3  in  single-phase  mode).  To  the  bottom  right  there  is  an  icon  that  allows 
immediate identification of the fact that the page is related to the GENERATOR measures. 

 

7.4.7.8

 

M.08 POWERS 2 

This  page  shows  the  reactive  powers  (kvar),  and  the  apparent  powers  (kVA)  on  individual 
phases and globally (for single-phase systems, the information related to phases 2 and 3 are 
replaced by dashes). To the bottom right there is an icon that allows immediate identification 
of the fact that the page is related to the GENERATOR measures. 

7.4.7.9

 

M.09 ENERGY 

This  page  shows  the  active  and  reactive  power  counters  (partial  and  total)  counted  by  the 
controller board when the loads are connected to the generator. 

The active power is counted only if positive (it is not counted in the event of reversed power). 
The reactive power is counted in module (the counter goes up both with capacitive loads and 
with inductive loads). 

On  this  page  you  can  reset  to  zero  the  partial  counters  individually.  To  this  purpose  it  is 
necessary to: 

 

Press and hold ▼: one of the counters will be highlighted.  

 

Use the vertical scrolling buttons ▲ and ▼  to select the counter you want to reset to 
zero. 

 

Press and hold the 

AUTO

 

and ▼ for five seconds. 

 

Press and hold button ▲ to deselect the counter. 

Attention: from version 01.08, if a password has been configured in parameter P.0001 ("user" 
protection  level),  it  will  not  be  possible  to  reset  the  counters  until  this  password  is  entered 

Содержание GC250

Страница 1: ...Technical Manual GC250 File name EAAM057608EN docx Rev 08 Date 23 05 2019 ID Document EAAM0576 Product GC250...

Страница 2: ...1 Modified par 3 Modified Par 4 1 Modified Par 5 11 04 25 07 2017 141 Modified table on par 5 page 20 Added par 11 11 05 11 12 2017 141 Modified table on par 3 page 16 Modified par 11 10 06 23 10 2018...

Страница 3: ...UEL SOLENOID Fuel solenoid command 26 5 5 T 09 D Energizing and checking the operation of the recharge alternator 28 5 5 1 T 09 D Input used as analogue input 29 5 5 2 T 09 D Input used as analogue in...

Страница 4: ...ify a parameter 79 8 2 3 Set up limits 80 8 3 Exit from programming 80 8 4 Loading default values 80 8 5 Protection password 81 8 5 1 Password for commands from serial port USB 82 9 Operation sequence...

Страница 5: ...06 Maximum current 111 07 Manual stop while in AUTO 113 08 Operating conditions failure 113 13 Mains circuit breaker MCB not closed 114 14 Genset circuit breaker GCB not closed 114 16 Short circuit o...

Страница 6: ...ow coolant level from CAN BUS 130 137 Low battery voltage from CAN BUS 130 142 Minimum oil pressure from CAN BUS 130 144 Low oil pressure from CAN BUS 130 158 High oil temperature from CAN BUS 131 159...

Страница 7: ...EAAM057608EN GC250 Technical Manual vii 11 8 Non volatile memory 141 11 9 Plant name 142 11 10 Power saving mode 142 11 11 CAN BUS connection with engines 143...

Страница 8: ...46 108 DIF 4003 46 108 DIF 4004 46 108 DIF 4011 46 108 DIF 4013 46 108 DIF 4014 47 108 DIF 4021 47 109 DIF 4023 47 109 DIF 4024 47 109 DIF 4031 47 109 DIF 4033 47 109 DIF 4034 47 109 DIF 4051 47 109 1...

Страница 9: ...EVT 5000 72 P P 0000 64 67 81 82 P 0001 63 64 67 81 82 P 0002 81 82 P 0003 81 82 P 0004 82 84 85 97 99 103 104 106 107 123 P 0101 49 92 110 111 112 114 124 125 126 136 P 0102 92 93 110 111 112 114 12...

Страница 10: ...132 P 0401 133 134 P 0402 133 P 0403 133 P 0404 127 135 P 0405 133 P 0406 133 P 0418 84 126 140 P 0419 84 140 P 0420 84 126 140 P 0421 95 126 141 P 0422 95 126 141 P 0423 95 126 141 P 0424 121 138 139...

Страница 11: ...ST_028 36 ST_032 36 ST_033 36 ST_035 36 ST_036 36 ST_038 36 ST_039 36 ST_040 36 ST_041 36 ST_064 36 ST_065 36 ST_068 36 ST_069 36 ST_070 36 ST_071 36 ST_072 36 ST_073 36 ST_074 36 ST_075 36 ST_080 37...

Страница 12: ...read understand and observe the precautions and warnings in this manual This manual contains the following indications WARNING This indication is used in the safety messages of the manual when there a...

Страница 13: ...fore they are subject to both hardware and software modifications without notice Some of the features described in this manual may therefore differ from those present in your device 1 4 Although most...

Страница 14: ...ction the following is a code for the configuration of the ANALOGUE outputs AVF ANALOGUE Virtual Function the following is a code for the configuration of the virtual ANALOGUE inputs EVT Event the fol...

Страница 15: ...EAAM057608EN GC250 Technical Manual 15 2 GC250 Front view Back GC250...

Страница 16: ...from HW E611215610001 and FW EB02502560104 Maximum power consumption in operating conditions siren LCD lamp digital inputs active communicating CANBUS analogue inputs to GND static outputs and D not...

Страница 17: ...0VDC Minimum voltage applicable 24VDC The input T 16 can be configured as analogue input for the measurement of the voltages see below Statics Outputs Four independent configurable outputs to battery...

Страница 18: ...ted with maximum consumption of 250mA from USB port CANBUS Connection CanBus connection without galvanic isolation with protocol SAEJ1939 and MTU for the connection to ECU engine control Fix internal...

Страница 19: ...ture ambient may vary between 30 C and 60 C 4 2 Due to the high voltages connected to the measurement circuits of the controller all conductive parts of the electrical panel should be connected to the...

Страница 20: ...VDC Output and D signal detection analogue input in configurable voltage 2 JB T 12 Analogues reference Configurable resistor sensors digital inputs 10 poles x2 5mm 2 screw terminal T 13 Fuel level T 1...

Страница 21: ...U Not used Available usable according to the plant requirements and the primary function provided for the terminal Some inputs can be configured and used both as digital inputs and as analogue inputs...

Страница 22: ...d By it is the case of the emergency plant in which the electric mains status is monitored the genset is usually started automatically in case of anomalies on the mains and it is stopped when anomalie...

Страница 23: ...EAAM057608EN GC250 Technical Manual 23 5 2 1 Principle connection diagram SSB plant...

Страница 24: ...24 GC250 Technical Manual EAAM057608EN 5 2 2 Principle connection diagram SPM plant...

Страница 25: ...be used but can generate operating problems and may require particular care as the use of insulation current transformers for the voltage measurements of Mains and Genset Although the device is prote...

Страница 26: ...s necessary to use an external relay The controller activates this command when motor start is required and deactivates it automatically within 200 300ms from the instant when it recognizes the motor...

Страница 27: ...ngine does not stop until it receives the explicit arrest command By default the positive auxiliary output T 05 is configured for the command of arrest during energizing You can configure any other ou...

Страница 28: ...when the engine is no longer acknowledged as started with a method whatsoever voltage frequency rpm D voltage oil pressure the command is kept active for 30s continuously and then is deactivated activ...

Страница 29: ...four digital outputs entirely programmable When activated they bring themselves to the positive supply voltage on the T 02 supply terminal The rated capacity of each output is 500mA the total power is...

Страница 30: ...s DOF 2004 MCB steady opening command DOF 2034 GCB steady closing command The GCB command is used to connect the loads to the generator The MCB command is used to connect the loads to the mains Two co...

Страница 31: ...the command before the changeover is completed so to let SIRCOVER not to be subject to blocks Instead reset the P 0219 parameter because the pause between mains and genset and vice versa is ensured by...

Страница 32: ...roller still singularly for each output using parameter P 3000 for the outputs on the controller 6 bit in total A zero bit means that the output is normally on standby and starts operating when the re...

Страница 33: ...Auto It activates when the controller is in AUTOMATIC mode DOF 3004 Test It activates when the controller is in TEST mode DOF 3005 Remote start It activates when the controller is in REMOTE START mode...

Страница 34: ...um coolant temperature from contact 034 Maximum coolant temperature from analogue sensor 035 High oil temperature from analogue sensor 037 Start battery low voltage 038 Start battery high voltage 039...

Страница 35: ...014 Genset circuit breaker not closed 023 Mains circuit breaker not open 024 Genset circuit breaker not open 5 6 4 AND OR logics The AND OR logics are basically a list of boolean conditions true false...

Страница 36: ...11 Blocks total ST_012 Unacknowledged warnings total ST_014 Unacknowledged deactivations cumulative ST_015 Unacknowledged blocks total ST_016 Presence of mains voltage frequency ST_017 Mains out of to...

Страница 37: ...TO button ST_306 START button ST_307 UP button ST_308 DOWN button ST_320 Status 01 from engine management by file ST_321 Status 02 from engine management by file ST_322 Status 03 from engine managemen...

Страница 38: ...potential T 12 The four values of the voltage measured on terminals and their related value of sensors resistance are displayed on page S 07 The inputs have a useful field of resistive measure betwee...

Страница 39: ...ectric mass of the engine or to the negative limit of the starting battery The system is able to efficiently compensate for both positive and negative potentials ranging between 2 7VDC and 3 5VDC with...

Страница 40: ...d the actions in case of out of threshold P 4013 and P 4016 for input T 13 INFORMATION the thresholds defined here do not depend on any threshold set within the menus Protections for example for the c...

Страница 41: ...eral X X X X AIF 1100 Oil temperature VDO X X AIF 1101 Oil temperature general X X X X AIF 1110 Coolant temperature VDO X X AIF 1111 Coolant temperature general X X X X AIF 1200 Oil level VDO X X AIF...

Страница 42: ...set a saturation limit on one end or on both ends of the curve In fact the controller board extends to infinity the first and last segments of the curve Being horizontal whatever value the measure to...

Страница 43: ...T 17 DIF 0000 Not used T 18 DIF 4201 Emergency stop T 19 DIF 2501 Genset start inhibition WARNING input T 18 is by default configured to manage the emergency stop command signal for safety reasons thi...

Страница 44: ...when the related terminal is not connected to anything The logic status of the input can be inverted with respect of the physical status by selecting the box Reverse polarity in the input configuratio...

Страница 45: ...mode of the controller switches from AUTO to TEST the input does nothing if the controller is not in AUTO or if the automatic intervention of the genset is required When it becomes inactive the statu...

Страница 46: ...MCB status Yes An input configured in this way is used to activate early warnings in the event of a discrepancy between the controls to the switch given by the board and the status of the same switch...

Страница 47: ...ption language dependant is activated This function can be also used for the Fuel pump management see par 11 1In fact every digital input can have an AND OR logic associated which determines its statu...

Страница 48: ...ection Connect the neutral if any N to the terminal T 28 Connect phase L to the terminal T 26 Parameters P 0119 allows to select the three phase single phase mode For CAT III use the maximum working v...

Страница 49: ...ect the three phase single phase mode For CAT III use the maximum working voltage is 300Vac phase neutral and 520Vac phase to phase Maximum voltage to ground is 300 Vac The controller board uses phase...

Страница 50: ...t situations and for a time lower than 3s such as measuring over currents or short circuit currents on the system using an algorithm to compensate for the saturation of the measurement circuits The TA...

Страница 51: ...and it is not to be considered a device fault WARNING When the device is supplied by the sole USB port it is not to be considered operative and must not be used to command the genset The PC to be con...

Страница 52: ...munication parameters see documents 4 5 e 6 The CAN BUS interface of the GC250 is not galvanically isolated Connections Connect terminal T 20 to terminal CAN_H of the engine s control unit Connect ter...

Страница 53: ...EAAM057608EN GC250 Technical Manual 53 7 7 1 Fig 1 GC250 Front Panel KEY 1 Push button 2 Indicators The controls consist of 5 buttons 1a 1b The front panel also has 5 luminous indicators 2a 2b...

Страница 54: ...it pressed at the same time as the START button allows access to the special functions AUTO By pressing the button for around half a second the controller provides for the automatic management of the...

Страница 55: ...he operating mode is TEST Flashing at 90 indicates that the operating mode is REMOTE START The Gen set control module is in another operating mode MANUAL Indicates that the operation mode is MANUAL In...

Страница 56: ...sing the P 0493 parameter you can force the lamp to stay always on when is engine is started 7 4 2 Contrast adjustment Depending on the environmental temperature conditions the contrast may require ad...

Страница 57: ...direction or to the other By keeping pressed for at least one second the arrow DOWN it is selected and displayed the desired mode To view the pages inside the mode you can use the buttons UP and DOWN...

Страница 58: ...gh the various pages using e buttons 7 4 6 1 S 01 STATUS Page S 01 displays information on the system status It contains The controller operation mode o Controller in OFF RESET mode o Controller in Ma...

Страница 59: ...e shown alongside an elapsing time for example during engine cooling down the residual time is shown 7 4 6 2 S 02 ANOMALIES The page S 02 is automatically displayed in case a new anomaly arises For ev...

Страница 60: ...conds The engine diagnostic codes are stored even if the engine deactivates them until the yellow red Can Bus indicator light warning is acknowledged Anomalies 252 253 254 255 referred to expansion mo...

Страница 61: ...sequence STATO FISICO the controller displays the electric level active or not active high or low really present on the input it can be opposite compared to the corresponding logic status Displayed in...

Страница 62: ...ows the Phase to Phase concatenated voltages and the frequency of the generator in addition to the rotation direction of the phases clockwise or counter clockwise For three phase systems the phase to...

Страница 63: ...r phase 2 and 3 in single phase mode To the bottom right there is an icon that allows immediate identification of the fact that the page is related to the GENERATOR measures 7 4 7 8 M 08 POWERS 2 This...

Страница 64: ...tio is 30 times higher than alternator frequency 7 4 8 2 E 02 ENGINE 2 It contains other measurements for engine management Starting Battery voltage V measured by the controller Fuel level in the tank...

Страница 65: ...ed by CAN BUS are shown in this page The number and type of available measures depend on the engine type Not available measures are shown with dashes If no information is available the page is not sho...

Страница 66: ...mmunication to the engine is enabled P 0700 different from zero Some engine measures acquired by CAN BUS are shown in this page The number and type of available measures depend on the engine type Not...

Страница 67: ...ow DPF Diesel Particulate Filter DOC Diesel Oxidation Catalyst SCR Selective Catalyst Reduction DEF Diesel Exhaust Fluid EST Exhaust System Temperature From version 1 07 the controller fully supports...

Страница 68: ...state not an anomaly If however the condition remains for a long time and the soot level in the filter becomes extremely high the ECU activates a diagnostic code with red lamp icon with a STOP sign sh...

Страница 69: ...mum of 10 seconds then the parameter is reset to 0 Automatic If the ECU can it carries out a regeneration cycle which involves overheating the emission treatment system and derating the engine Followi...

Страница 70: ...for the engine Attention since the descriptions are defined in the external file they do not fit the language selected on the controller typically they are in English 7 4 9 History logs H xx When in o...

Страница 71: ...which the event occurred the operation mode of the controller the engine the generator the mains and the change over in that moment If the event is an anomaly measures described for the analogue arch...

Страница 72: ...nput EVT 1056 1 00 Command for start in TEST mode from serial port EVT 1058 1 00 Command for start in TEST mode from clock calendar EVT 1062 1 00 Starting command for failure to close MCB EVT 1070 1 0...

Страница 73: ...h show different information depending on the selected page The first page shows the numerical code of the event 0024 in the given example and one or more icons which identify the event W024 GCB close...

Страница 74: ...e generator at the time of recording frequency and voltages The third page displays all the values of the load currents and powers at the time of recording currents apparent power active and reactive...

Страница 75: ...e of the display The second line shows the record currently displayed out of the total number of records the maximum number of records is 16 The fourth line shows the recording date and time The sixth...

Страница 76: ...on of the problem if available The more recent record is the one associated to the highest number Using the and push buttons it is possible to scan all the records The controller uses only one page of...

Страница 77: ...ommended as it simplify a lot the programming operations In this paragraph the general programming structure and the operating procedure to read and or modify parameters are described You can use the...

Страница 78: ...iliary functions history logs and serial communication 5 COMMUNICATION This menu configures the communication via USB 7 CAN BUS The engine menu 7 CAN BUS allows to set the way the controller communica...

Страница 79: ...evious menu 8 2 2 Modify a parameter You may only modify parameters displayed between square brackets A parameter between major minor symbols cannot be modified In this case it could be necessary to s...

Страница 80: ...where 4 is the value associated to function 3 8 to function 4 32 to function 6 e 128 to function 8 Attention the value must be set with the hexadecimal noting o 255 FF o 0 00 o 172 AC 8 2 3 Set up lim...

Страница 81: ...he menu 1 1 2 Password path 1 System 1 1 Security 1 1 2 Password The 0 value for these parameters indicates not set password If a password gets lost it is possible to reconfigure it by logging in with...

Страница 82: ...programmable without entering any code in P 0000 When the user enters III in P 0000 he can modify all parameters associated to installer and end user When entering III in P 0000 the operator is identi...

Страница 83: ...by the genset The access to the programming is not allowed REMOTE START this working mode is almost identical to AUTO It only differs for the fact that the engine is started in any case automatically...

Страница 84: ...the engine sequence description All possible TEST function activation modes are described below TEST mode is indicated by means of a flashing spy AUTO on the panel 50 on 50 off You can shift to TEST...

Страница 85: ...in REMOTE START mode in case the serial connection is interrupted before receiving the opposite command Parameters can be password protected P 0004 refer to par 8 5 1 which has to be sent before ever...

Страница 86: ...the device to use the measures of the mains voltages and frequency the operator has to set the mains rated voltage through parameter P 0116 By means of the digital input configured with the feature DI...

Страница 87: ...m up to four different checks that can be individually disabled They are described individually below also with examples remember that disabling both voltages and frequency checks is not possible in t...

Страница 88: ...P 0204 Maximum voltage threshold 110 0 440 P 0201 Maximum hysteresis 2 5 10 The hysteresis on the various thresholds is calculated as half the difference between P 0204 and P 0203 However it is limite...

Страница 89: ...direction is counter clockwise the mains is seen as Out of tolerance In case a clockwise rotation direction is required please set 2 in P 0239 in case the rotation direction is counter clockwise the m...

Страница 90: ...are defined Bit 0 used when the controller is in OFF RESET mode In this mode the controller does not normally manage the mains presence delay to re power the loads as soon as possible since they are...

Страница 91: ...r three phase voltage and frequency in order to protect the loads and the generator itself from operating outside its tolerance thresholds To connect the generator to the controller see par 5 10 9 3 1...

Страница 92: ...etting to zero the relevant parameter that specifies the delay respectively P 0306 and P 0308 Even if the protections are disabled thresholds are however used in order to define the frequency status t...

Страница 93: ...e voltage was in the E band and now it is in D band it is considered however In tolerance On the other hand if it was in C band and now is in D band it is considered Low Such statuses are managed for...

Страница 94: ...ollowing internal statuses ST 024 Generator voltage frequency present ST 025 Generator out of tolerance or absent ST 026 Delay for generator within tolerance ST 027 Generator within tolerance ST 028 D...

Страница 95: ...oller also makes available to the use of AND OR logics the internal status ST 081 Clock calendar starting inhibition 9 5 The device can start stop and protect the engine by means of a series of thresh...

Страница 96: ...tor phase is higher than P 0227 From generator frequency Two thresholds are available P 0228 e P 0229 which have to be both different from zero and P 0229 has to be major than P 0228 otherwise this ch...

Страница 97: ...st once you select mode MAN and it is necessary to press it again to start the engine Furthermore there are two possible sequences of manual start up If bit 1 of parameter P 0495 Keyboard options is t...

Страница 98: ...h The starting check status if we are in MAN Actually the given command could be enough for the engine which therefore could get started In this state the engine has to be checked for a maximum time o...

Страница 99: ...STER 102 write value 21 standard stop or 22 emergency stop In MAN o Pressing STOP from the controller panel In AUTO o When the automatic intervention of the genset is no more requested INFORMATION nor...

Страница 100: ...an automatic stop cycle as situations can be happen where it is difficult to restart the engine if it was not completely stopped During the stop waiting stop waiting phase all engine commands deactiv...

Страница 101: ...coil if any of the circuit breaker The controller enables this output when it must open the breaker and disables it when it must close the breaker the real closing command will be activated with at le...

Страница 102: ...ng command The controller enables this output when it wants to close the circuit breaker ensuring that DOF 2031 has been active for at least 0 5 seconds the output stays active even with circuit break...

Страница 103: ...hen closes the desired breaker In this case it is possible to configure the duration of the pause with both switches open by means of P 0219 parameter contactors controls exchange time 9 6 5 MAN or TE...

Страница 104: ...g of the GCB and subsequent closing of the MCB if possible See also the description of EJP function on par 11 4 You can use a command from the serial port Such command is temporary only lasts 30 secon...

Страница 105: ...eate hazards for the loads but not immediately for the engine For this reason the controller opens immediately the GCB breaker then it stops the engine with standard procedure that is with the cooling...

Страница 106: ...SB The commands can be protected by a password P 0004 which has to be sent before any command and can be deactivated through a digital input DIF 2706 To send the command it is necessary to write in se...

Страница 107: ...DING REGISTER 101 write the password configured with the parameter P 0004 HOLDING REGISTER 102 write value 53 Using a digital input configured with the feature DIF 2001 Alarms reset command When the i...

Страница 108: ...for each digital input What stated above is true also for generic anomalies They will not be described in the following paragraphs because they will be infinite repetitions of the same description for...

Страница 109: ...igh value from analogue input if the anomaly is activated when the measure is higher than the threshold Low value from analogue input if the anomaly is activated when the measure is lower than the thr...

Страница 110: ...arameters P 0101 Number of generator phases P 0102 Generator rated voltage P 0202 Hysteresis of generator measures P 0303 Threshold for minimum voltage P 0304 Delay for minimum voltage To disable P 03...

Страница 111: ...gine idle D P 0231 Threshold for engine started D P 0357 Action for belt break P 0349 Delay belt break To disable P 0349 0 Enabled in MAN AUTO TEST REMOTE START This protection is enabled only if the...

Страница 112: ...t the maximum current threshold with the parameter P 0309 as a percentage of the rated current In the previous example setting a 350 A maximum threshold requires entering 121 in parameter P 0309 Set t...

Страница 113: ...tting in parameter P 0495 the value 1 It is activated when pressing the STOP button on the front panel or sending a stop command via USB while in AUTO TEST or REMOTE START 08 Operating conditions fail...

Страница 114: ...tal inputs of the controller is configured to acquire the MCB status feature DIF 3001 MCB breaker status in parameter P 2001 or equivalent for the other inputs and if a time other than zero has been s...

Страница 115: ...gine start stop phases It activates if the generator frequency exceeds threshold P 0331 continuously for time P 0332 INFORMATION Parameter P 0331 is expressed in percentage with respect to P 0105 21 E...

Страница 116: ...of input T 16 or equivalent for other inputs P 2002 Delay for input T 16 or equivalent for other inputs To disable P 2002 0 Enabled in MAN AUTO TEST REMOTE START This protection is enabled only when...

Страница 117: ...1 Function of input T 16 or equivalent for other inputs P 2002 Delay for input T 16 or equivalent for other inputs To disable P 2002 0 Enabled in MAN AUTO TEST REMOTE START It is enabled only when one...

Страница 118: ...onfigured to use the analogue fuel level sensor P 4009 suitably configured or if said sensor is physically connected to the device terminal It activates if the level measure remains continuously above...

Страница 119: ...ne protection Related parameters P 2001 Function of input T 16 or equivalent for other inputs P 2002 Delay for input T 16 or equivalent for other inputs P 0216 Time of engine protection mask To disabl...

Страница 120: ...acquires the measure of the engine oil temperature It can acquire it from analogue input T 15 P 4025 or from CAN BUS P 0700 other than zero It is only enabled if the controller has been started by th...

Страница 121: ...ck based on the settings of the P 0425 parameter It cannot be cancelled even disconnecting the controller s power supply Only possible setting P 0424 again setting it to zero to disable the function o...

Страница 122: ...l status of low pressure which occurs at start up 43 Low oil pressure from contact Icon Type Warning Category Engine protection Related parameters P 2001 Function of input T 16 or equivalent for other...

Страница 123: ...ault input T 18 is configured with the function of emergency stop This interlock can be activated even if another one is already active It activates if the input that acquires the external contact fun...

Страница 124: ...01 Number of generator phases P 0102 Generator rated power P 0106 Generator nominal power P 0317 Threshold current asymmetry rated current P 0318 Delay for current asymmetry To disable P 0318 0 Enable...

Страница 125: ...he controller if the command for the fuel solenoid is activated and is disabled when the engine is started stopped In addition the generator voltages and frequency must be within the tolerance range a...

Страница 126: ...and for the fuel solenoid is activated and is disabled in the engine start stop phases In addition the generator voltages and frequency must be within the tolerance range and the load must be changed...

Страница 127: ...Warning Block Deactivation Category General Related parameters P 0700 Engine type P 0703 Command level via Can Bus ECU P 0709 Signalling for Can Bus ECU failure Enabled in MAN AUTO TEST REMOTE START...

Страница 128: ...1 Maximum time without messages from engine To disable P 0711 0 no for MTU engine Enabled in MAN AUTO TEST REMOTE START It s enabled only if CAN BUS is configured P 0700 other than zero For MTU MDEC e...

Страница 129: ...n is enabled only if the board is connected to the engine via the CAN BUS P 0700 different from zero It is activated when the engine signals the coolant high temperature state over the CAN BUS 134 Max...

Страница 130: ...con Type Warning Category Engine protection Related parameters P 0700 Engine type P 0704 Anomalies deactivation mask from Can Bus To disable bit 9 of P 0704 on Enabled in MAN AUTO TEST REMOTE START Th...

Страница 131: ...activated when the engine signals the high oil temperature state over the CAN BUS 159 Maximum oil temperature from CAN BUS Icon Type Alarm Category Engine protection Related parameters P 0700 Engine t...

Страница 132: ...e via the CAN BUS P 0700 different from zero It is activated when the engine signals the active state of its red lamp over the CAN BUS Using bit 13 of P 0704 it is possible to configure the protection...

Страница 133: ...ception solenoid on the pump line DOF 1034 Fuel pump solenoid command In BoardPrg3 we have the menu 4 2 1 for pump configuring Anyway you can set each individual parameter directly from the controller...

Страница 134: ...212 closed if the level is below the low level threshold Start up contact input with feature DIF 3301 closed if the level is below the pump start up threshold Stop contact input with feature DIF 3302...

Страница 135: ...andbook This function allows to monitor the trend of the active power in order to diagnose A low load condition A high load condition to disconnect in case a part of the loads It is necessary to choos...

Страница 136: ...part of the loads is disconnected the power will decrease If the lower threshold is too high the output will be disabled and this could cause the load to be reconnected with a pendulum effect 11 3 Al...

Страница 137: ...output signals coherent with said function The EJP function allows to start the engine and warm it before mains failure so when it will happen loads can be immediately changed over on gen set reducing...

Страница 138: ...s to AUTO mode due to mains on performs the engine stop with cooling cycle 11 5 The controller can automatically inform the operator about programmed maintenance by means of an engine hours counter 11...

Страница 139: ...ed as its value changes and it is then important to know when values are saved and how to be sure that they are saved before removing supply from the board Counters are saved all together and in the s...

Страница 140: ...rameter each bit of the parameter corresponds to a day of the week The value you must set for the parameter is the sum of the value field of the following table for the days needed Bit Value Day 0 1 S...

Страница 141: ...e time set with P 0423 refers to the following days For example in case an automatic gen set start is required only Monday through Friday between 08 00 and 18 00 you must set P 0421 62 2 4 8 16 32 P 0...

Страница 142: ...et parameter P 0590 Delay before energy saving to a value other than zero To enable the mode you must Turn off the engine Disconnect any ongoing communications via USB eg with BoardPrg3 Set the contro...

Страница 143: ...gh P 0700 parameter among the list of allowed engines Then it is possible to decide whether only to receive information from the ECU of the engine or also send controls P 0703 detailed in the above me...

Страница 144: ......

Страница 145: ...fort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use this information The disclosure by any means of this document to third partie...

Отзывы: