User’s Manual 5
DIP 5(analog on CANBUS):
enables/disables transmission via Can bus of the water temperature
and oil pressure sensors connected to the analog inputs of the DIPOT module (connector J2). In
the Can Bus version of the receiving device, the Can is always enabled, regardless of the state of
this switch, if SWE dip 7 is ON (REMOTE CONTROLS).
DIP 6
(CCW/CW):
lets you switch the current loop output in relation to data control (and then
switch from CW to CCW operating mode). In CW mode, the request with a CANBUS/Modbus
message or from the UP button, for an increment in the command, will result in a drop in the value
of the output current while in CCW mode, the request with a CANBUS/Modbus message or from
the DOWN button, for a decrease in the command, will result in an increase in output current.
DIP 7
(REMOTE/LOCAL CONTROL):
in "Local" mode the up/down/reset buttons are acquired
and let you change the current loop output value. In "Remote" mode, the current-loop output value
is determined by the CANBUS or Modbus command. With version RS485 in "Remote" mode, the
value of the MIN, MAX, RESET and RAMP trimmer is set in the "Holding register.
DIP 8(Rpm1500/1800 from CANBUS/DIGITAL INPUT):
determines if the nominal speed of the
motor (1500 or 1800 rpm) is automatically detected by the CANBUS or digital input J3-2. (If the
input is active, the nominal speed is 1800 rpm, if the input is inactive the nominal speed is 1500
rpm).
Switch
SWD
is a 4-way switch and sets the properties of the available serial port on stereo jack connector
J6
and connector
J4:
DIP 1 (120R ON/OFF)
: lets you connect/disconnect the 120R termination resistor on serial port
RS485 of
J6
(only if necessary and if the port is set as RS485).
DIP 2 (Enable/disable Serial port)
: enables/disables the serial port on stereo jack
J6.
In the versions with isolated RS485 (
E6102094300xx
and
E6102094301xx)
serial port of connector
J4
is shared with connector
J6
. Use
SWD
dip 2 to select which port should be used. The serial ports on
J4
and
J6
cannot operate simultaneously. If the serial port is used on connector
J6
, disconnect the female
connector on
J4.
In versions with CANBUS (
E6102094020xx
and
E6102094303xx)
the serial port on connector
J6
is
always available.
DIP 3 (RS232/RS485)
: configures the serial port on Stereo jack
J6
as RS232 or RS485 (not
isolated).
DIP 4 (9600/19200 Bd):
sets the baud rate used by the serial port on Jack (
J6
) and also that of
isolated RS485 serial port (
J4
) if the product is version RS485.
The
SWB
switch is a 2-way switch and sets the scale of the current loop used:
from 0 to +20 mA
SWB-1 OFF SWB-2 OFF
from -10mA to +10mA
SWB-1 ON
SWB-2 ON
from -20mA to +20 mA
SWB-1 ON
SWB-2 OFF
The
SWC
switch is a 4-way switch that lets you enable the voltage insulator function (Setting
ON
on
switch no. 1).