28
D-PRO Protection relay Technical Manual
•
DIF.2718
(”Protections disabling - Level 8”). The controller inhibits the intervention of
the protections configured in the parameter P.0208.
The bit parameters P.0201, P.0202, P.0203, P.0204, P.0205, P.0206, P.0207 and P.0208
are defined as follows:
Bit
Value
Description
0
1
Disable protection 27
1
2
Disable protection 27T
2
4
Disable protection 32P
3
8
Disable protection 32Q
4
16
Disable protection 46
5
32
Disable protection 47
6
64
Disable protection 50
7
128
Disable protection 50N
8
256
Disable protection 50V
9
512
Disable protection 51
10 1024
Disable protection 51N
11 2048
Disable protection 51V
12 4096
Disable protection 59
13 8192
Disable protection 59N
14 16384
Disable protection 81U
15 32768
Disable protection 81O
16 65536
Disable protection 87G
17 131072
Disable protection 87T
18 262144
Disable protection 32RP
19 524288
Disable protection 32RQ / 40
20 1048576
Disable protection 64