D-PRO Protection relay Technical Manual
P.3003
Output 01 delay.
P.3004
Output 2 (JL_3)
Output 02 function.
P.3005
Output 02 type (activation mode).
P.3006
Output 02 delay.
P.3007
Output 3 (JI_4)
Output 03 function.
P.3008
Output 03 type (activation mode).
P.3009
Output 03 delay.
P.3010
Output 4 (JI_1)
Output 04 function.
P.3011
Output 04 type (activation mode).
P.3012
Output 04 delay.
By default, all the outputs activate when required by the related function. Using BoardPrg3, it
is possible to invert the
activation by simply selecting the box “Inverted polarity” on the top of
the configuration page of each output.
•
A zero-bit means that the output is normally in standby and starts operating when required
by the related function.
•
A one-bit means that the output is normally operating and goes in standby when required
by the related function.
The map of the outputs present on the controller is:
BIT
Value
Output
0
1
Output 1 (JL-1)
1
2
Output 2 (JL_3)
2
4
Output 3 (JI_4)
3
8
Output 4 (JI_1)
By default, all bits are set to zero.
The status of the digital outputs is displayed by the proper LEDs (OUT1, OUT2, OUT3, OUT4)
mounted on the controller.
The digital outputs can be used directly as command for controller external devices or as
signalization of particular operating conditions. Below the functions adjustable on the digital
outputs:
Code
Description
Delay
+ mode
Note
DOF.0000
Not used
DOF.0103
AND/OR logics.
The output status results from the combination of the
AND/OR logics.
DOF.1001
Protection enabling (ENABLE)
YES
It activates the output when at least one protection is
enabled (the parameters are configured correctly and
no protections disabling input is active)
DOF.1002
Protection activation (ACTIVE)
YES
It activates the output when at least one protection is
started (the threshold has been exceeded but the
time configured has not passed)
DOF.1003
Protection intervention (TRIP)
YES
It activates the output when at least one protection
has triggered (the threshold has been exceeded for
the time configured) The reset depends on the
activation of the alarms reset input.
DOF.2001
Protections configuration - level 1
YES
It activates the output if one of the protections
configured in the parameter P.0221triggered.
DOF.2002
Protections configuration - level 2
YES
It activates the output if one of the protections
configured in the parameter P.0222triggered.
DOF.2003
Protections configuration - level 3
YES
It activates the output if one of the protections
configured in the parameter P.0223triggered.
DOF.2004
Protections configuration - level 4
YES
It activates the output if one of the protections
configured in the parameter P.0224triggered.
DOF. 3031
Frequency within tolerance
YES
It activates when the frequency parameters are within
normal operation. It activates if there is at least one
frequency within tolerance