10.3 Operation
Problem
Presumed cause and solution
Input value does not
change.
• The sensor may be out of order. Change the sensor.
• Check whether input and output wires are securely connected
to the I/O terminals of the instrument.
Ensure that input and output wires are securely connected to
the I/O terminals.
• Check whether the wiring of input and output is correct.
No output
• Check whether Output 100% and Output 0% value have been
set to suitable values.
• Check whether Output type has been selected correctly during
Output type selection, and whether Output Normal/Reverse
has been selected correctly during Output Normal/Reverse
selection.
11. Character table
Default values are indicated in the following tables.
Function group
For the SE2 , CH1 and CH2 have respective setting items.
For the SEW , Input/Output 1, Output 2 have respective setting items.
Display
Setting item
Default value
Data
Input type
DC voltage (SE2U, SE1U, SEWU)
Thermocouple input range
K -200 to 1370
(SE2E, SE1E)
RTD input range
Pt100 -200 to 850
(SE2R, SE1R)
DC current input range
4 to 20mA DC -1999 to 9999 (SE2A, SE1A)
DC voltage input range
1 to 5V DC -1999 to 9999
(SE2U, SE1U, SEWU, SE2V, SE1V)
Decimal point place
No decimal point
Output 0% value
-1999 (SE2U, SE2A, SE2V, SE2P,
SE1U, SE1A, SE1V, SE1P,
SE1D, SE1D-F, SEWU, SEWD)
-200
(SE2E, SE2R, SE1E, SE1R)
Output 100% value
9999 (SE2U, SE2A, SE2V, SE2P,
SE1U, SE1A, SE1V, SE1P,
SE1D, SE1D-F, SEWU, SEWD)
1370 (SE2E, SE1E)
850
(SE2R, SE1R)
Filter time constant
0.0 sec
Sensor correction
0
(SE2U, SE2A, SE2V, SE2P,
SE1U, SE1A, SE1V, SE1P,
SE1D, SE1D-F, SEWU, SEWD)
0.0
(SE2E, SE2R, SE1E, SE1R)
Output type
4 to 20mA DC
Output Normal/Reverse
Normal
Burnout
Upscale (SE2E, SE2R, SE1E, SE1R)