17
(2) ACS-13A, JCL-33A, JCS-33A, JCM-33A, JCR-33A, JCD-33A
(Fig. 5.2.2-2)
Connection between LMD-100 and controller
(ACS-13A/JCL-33A/JCS-33A/
JCM-33A/JCR-33A/JCD-33A)
Connection between controllers
(ACS-13A/JCL-33A/JCS-33A/JCM-33A/JCR-33A/
JCD-33A)
Connect YA (-) to YA (-), YB (+) to YB (+) and SG to SG respectively, using a shielded wire.
Connect only one side of the shielded wire to the FG terminal so that current cannot
flow to the shielded wire.
If both sides of the shielded wire are connected to the FG terminal, the circuit will be
closed between the shielded wire and the ground. As a result, current will run
through the shielded wire, and this may cause noise.
Be sure to ground FG terminal.
Recommended cable: OTSC-VB 2PX0.5SQ (made by Onamba Co., Ltd.) or equivalent
(Use a twisted pair cable.)
Wiring example between LMD-100 and ACS-13A
(Fig. 5.2.2-2)
Terminal numbers for connection differ depending on a controller model as follows.
LMD-100
JCL-33A
JCS-33A
JCM-33A
JCR-33A
JCD-33A
15 YA (-)
10 YA (-)
13 YA (-)
10 YA (-)
11 YA (-)
11 YA (-)
16 YB (+)
11 YB (+)
14 YB (+)
13 YB (+)
14 YB (+)
14 YB (+)
17 SG
12 SG
15 SG
14 SG
17 SG
17 SG
(Fig. 5.2.2-2)
LMD-100
ACS-13A
Shielded wire
Shielded wire
Shielded
wire