background image

38

10.2 Auxiliary Function Setting Mode 1

To enter Auxiliary Function Setting Mode 1, press and hold the DOWN key and MODE key (in that order)
together for approx. 3 seconds in PV/SV Display Mode.

Character

Factory Default

Setting Item, Function, Setting Range

Set value lock

(Unlock): All set values can be changed.

(Lock 1): None of the set values can be changed.
(Lock 2): Only Alarm setting mode (p.14) can be changed.
(Lock 3): All set values – except the input type (p.18) – can be changed.

However, changed values revert to their previous value after
power is turned off because they are not saved in the
non-volatile IC memory. Do not change any setting items in
Auxiliary function setting mode 2 (pp.18 - 24). If any item is
changed in Auxiliary function setting mode 2, it will affect the
alarm value (A1 value - A4 value).

Sensor correction coefficient

• Setting range: -10.000 to 10.000

Sensor correction

• Setting range: -1000.0 to 1000.0

( )

Direct current, DC voltage input: -10000 to 10000 (The placement of the decimal

point follows the selection.)

Communication protocol

: Shinko protocol
: Modbus ASCII mode
: Modbus RTU mode
: Shinko protocol (Block read available)
: Modbus ASCII mode (Block read available)
: Modbus RTU mode (Block read available)

Instrument number

• Setting range: 0 to 95

Communication speed

: 2400 bps
: 4800 bps
: 9600 bps
: 19200 bps
: 38400 bps

Parity

: No parity
: Even
: Odd

Stop bit

: 1 bit
: 2 bits

Содержание JIR-301-M

Страница 1: ...DIGITAL INDICATOR JIR 301 M Instruction Manual ...

Страница 2: ...the inner assembly To prevent an electrical shock fire or damage to the instrument parts replacement may only be undertaken by Shinko or other qualified service personnel Safety Precautions To ensure safe and correct use thoroughly read and understand this manual before using this instrument This instrument is intended to be used for industrial machinery machine tools and measuring equipment Verif...

Страница 3: ...excessive force is applied to the screw when tightening the terminal screw or case may be damaged Do not pull or bend the lead wire on the terminal side when wiring or after wiring as it could cause malfunction Use a thermocouple and compensating lead wire according to the sensor input specifications of this instrument Use the 3 wire RTD according to the sensor input specifications of this instrum...

Страница 4: ...4 Characters used in this manual No character is indicated Indication Number 1 0 1 2 3 4 5 6 7 8 9 Indication Alphabet A B C D E F G H I J K L M Indication Alphabet N O P Q R S T U V W X Y Z ...

Страница 5: ...Mode 1 15 5 4 Auxiliary Function Setting Mode 2 18 5 5 Maintenance Mode 25 6 Operation 26 6 1 Operation 26 6 2 Switching SV Display Indication 26 6 3 How to Use the Alarm Output 26 6 4 How to Use the Event Input Function 26 7 Alarm Action 27 7 1 High Limit Alarm Low Limit Alarm 27 7 2 A3 High Low Limit Range Alarm Action 28 7 3 A4 High Low Limit Range Alarm Action 28 8 Specifications 29 8 1 Standa...

Страница 6: ...1 A2 and A3 outputs are standard features Alarm types 4 types for A1 A2 and 5 types for A3 as well as No alarm action and Energized De energized can be selected 1 Thermocouple 10 types RTD 2 types Direct current 2 types and DC voltage 4 types can be selected by keypad 2 Power supply voltage 100 to 240 V AC is standard When ordering 24 V AC DC enter 1 after the input code 3 Alarm 4 output A4 option...

Страница 7: ...2 0 to 20 Input MULTI RANGE Multi range input A1 A2 A3 A4 P24 P5 outputs A1 A3 3 A 250 V AC A2 3 A 250 V AC Power supply voltage Power consumption 100 to 240 V AC 50 60 Hz 10 VA Serial number No 165F05000 Manufacturing factory ID SF Fukuoka factory Compliant standards UL CSA RoHS RoHS directive compliant Ambient temperature 0 to 50 Manufacturer SHINKO TECHNOS CO LTD Inner assembly No Description E...

Страница 8: ...or When A2 output is ON the red LED is lit While A2 output is held maintained the red LED flashes A3 action indicator When A3 output is ON the red LED is lit While A3 output is held maintained the red LED flashes A4 action indicator When A4 output is ON the red LED is lit While A4 output is held maintained the red LED flashes A4 option Key Name Description UP key Increases the numeric value If Hig...

Страница 9: ...current is flowing No water oil or chemicals or where the vapors of these substances can come into direct contact with the unit Please note that the ambient temperature of this unit not the ambient temperature of the control panel must not exceed 50 122 if mounted through the face of a control panel otherwise the life of electronic components especially electrolytic capacitors may be shortened 3 2...

Страница 10: ...ert the instrument from the front side of the control panel 2 Attach the mounting brackets by the slots on the right and left sides of the case and secure the instrument in place with the screws Fig 3 4 1 Caution As the case of the JIR 301 M is made of resin do not use excessive force while tightening screws or the mounting brackets or case could be damaged 0 12 N m of torque is recommended ...

Страница 11: ...se malfunction Use a thermocouple and compensating lead wire according to the sensor input specifications of this instrument Use the 3 wire RTD according to the sensor input specifications of this instrument This instrument does not have a built in power switch circuit breaker and fuse It is necessary to install a power switch circuit breaker and fuse near the instrument Recommended fuse Time lag ...

Страница 12: ...ansmission output 2 T 2 option A4 A4 output A4 option A Direct current input DSB option 24V Power for 2 wire transmitter DSB option 4 2 Lead Wire Solderless Terminal Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown below 0 63 N m of torque is recommended Solderless Terminal Manufacturer Model Y type Nichifu Terminal Industries Co Ltd TMEV1 25Y 3 Japan Solderle...

Страница 13: ... K J R S B E T N PL C W Re5 26 Pt100 JPt100 Pt100 JPt100 4 20 mA DC 1 2 0 20 mA DC 1 2 0 1 V DC 1 0 5 V DC 1 1 5 V DC 1 0 10 V DC 1 4 20 mA DC 1 3 0 20 mA DC 1 3 Scaling high limit value 1 Input range and decimal point place can be selected 2 Connect a 50 shunt resistor sold separately between input terminals 3 Has a built in 50 shunt resistor If Power for 2 wire transmitter DSB option is ordered ...

Страница 14: ...low limit alarm value Setting range Refer to Table 5 2 1 A4 high limit value Sets A4 output high limit action point Available when Alarm 4 output A4 option is ordered or when High Low limit range alarm is selected in A4 type Setting range Refer to Table 5 2 1 Table 5 2 1 Alarm Type Setting Range High limit alarm Input range low limit to input range high limit 1 Low limit alarm Input range low limi...

Страница 15: ...sensor correction Current PV x Sensor correction coefficient Sensor correction value Refer to Input Value Correction p 17 Setting range 10 000 to 10 000 Sensor correction This corrects the input value from the sensor When a sensor cannot be set at the exact location where measurement is desired the sensor measured temperature may deviate from the temperature in the measurement location When using ...

Страница 16: ...peed Selects a communication speed equal to that of the host computer Available only when the Serial communication C5 option is ordered 2400 bps 4800 bps 9600 bps 19200 bps 38400 bps Parity Selects the parity Available when Serial communication C5 option is ordered or when Modbus ASCII mode or Modbus RTU mode is selected in Communication protocol No parity Even Odd Stop bit Selects the stop bit Av...

Страница 17: ...termine the PV after correction PV before correction 300 PV after correction 340 PV before correction 750 PV after correction 700 2 Calculate Sensor correction coefficient from Step 1 Y X Y X 700 340 750 300 0 8 3 Enter a PV value of 300 using an mV generator or dial resistor 4 Set Step 2 value as a Sensor correction coefficient 5 Read the PV 240 will be indicated 6 Calculate the sensor correction...

Страница 18: ... T 200 0 to 400 0 T 200 0 to 750 0 N 200 to 1300 N 320 to 2300 PL 0 to 1390 PL 0 to 2500 C W Re5 26 0 to 2315 C W Re5 26 0 to 4200 Pt100 200 0 to 850 0 Pt100 200 0 to 1000 0 JPt100 200 0 to 500 0 JPt100 200 0 to 900 0 Pt100 200 to 850 Pt100 300 to 1500 JPt100 200 to 500 JPt100 300 to 900 4 to 20 mA DC 2000 to 10000 Externally mounted 50 shunt resistor 0 to 20 mA DC 2000 to 10000 Externally mounted...

Страница 19: ...27 If A1 type is changed A1 value will default to 0 0 0 No alarm action High limit alarm Low limit alarm High limit with standby alarm Low limit with standby alarm A2 type Selects an A2 type See Section 7 1 p 27 Not available if Insulated power output P24 option or P5 option is ordered If A2 type is changed A2 value will default to 0 0 0 No alarm action High limit alarm Low limit alarm High limit ...

Страница 20: ...A1 output terminals 7 8 is not conducted OFF while A1 action indicator is lit A1 output is conducted ON while A1 action indicator is unlit A1 output will be substituted by A2 A3 or A4 output A1 output terminals will be substituted by A2 A3 or A4 output terminals as follows A2 output terminals 9 10 A3 output terminals 12 13 A4 output terminals 15 16 High limit alarm Energized High limit alarm De en...

Страница 21: ...lable if No alarm action or High Low limit range alarm is selected in A3 type Setting range 0 1 to 100 0 Direct current DC voltage input 1 to 1000 The placement of the decimal point follows the selection A4 hysteresis Sets A4 hysteresis Available only when Alarm 4 output A4 option is ordered Not available if No alarm action is selected in A4 type Setting range 0 1 to 100 0 Direct current DC voltag...

Страница 22: ...V DC output 0 10 V DC Equals 10 V DC output Setting range Transmission output 1 low limit to Input range high limit The placement of the decimal point follows the selection or input range Transmission output 1 low limit Sets the Transmission output 1 low limit value Standard 4 20 mA DC Equals 4 mA DC output Optional 0 20 mA DC Equals 0 mA DC output 0 1 V DC 0 5 V DC 0 10 V DC Equals 0 V DC output ...

Страница 23: ...nals 14 17 The Bottom HOLD function is cancelled by opening Event input terminals 14 17 Alarm HOLD 1 If any of A1 HOLD function to A4 HOLD function is set to Enabled and if the alarm is ON the alarm will be maintained by closing Event input terminals 14 17 The Alarm HOLD function will be cancelled by opening Event input terminals 14 17 While the Event input terminals 14 17 are open the Alarm HOLD ...

Страница 24: ...nction Enables Disables the A4 HOLD function Available when Alarm 4 output A4 option is ordered Not available if No alarm action is selected in A4 type If A4 HOLD function is set to Enabled and if the alarm is ON the alarm output ON status will be maintained until the following is conducted The FAST key is pressed for approx 3 seconds The power is turned OFF The HOLD is cancelled by the Event inpu...

Страница 25: ...ype Not available if Insulated power output P24 option or P5 option is ordered Output OFF Output ON A3 output ON OFF A3 output can be turned ON by the UP key and OFF by the DOWN key Not available if No alarm action or High Low limit range alarm is selected in A3 type Output OFF Output ON A4 output ON OFF A4 output can be turned ON by the UP key and OFF by the DOWN key Available when Alarm 4 output...

Страница 26: ...ay and the A2 value indicator is lit Not available if No alarm action is selected in A2 type Not available if Insulated power output P24 option or P5 option is ordered PV A3 value A3 value indication Indicates A3 value on the SV Display and the A3 value indicator is lit Not available if No alarm action or High Low limit range alarm is selected in A3 type PV A4 value A4 value indication Indicates A...

Страница 27: ...t terminals 9 10 A3 output terminals 12 13 A4 output terminals 15 16 A1 A2 A3 or A4 action indicator is lit when each output terminals are ON A1 A2 A3 or A4 action indicator is turned off when its output terminals are OFF A1 output terminals 7 8 ON A1 output terminals 7 8 ON or OFF A1 output terminals 7 8 OFF A1 output is in standby ...

Страница 28: ...ed A3 is turned ON while A1 or A2 is in standby If A1 or A2 hysteresis increases A3 ON span decreases When A1 or A2 delay time setting time increases A3 ON time increases If A1 or A2 delay time setting time is set while A1 or A2 delay time is working when power to the instrument is turned ON A3 is turned ON 7 3 A4 High Low Limit Range Alarm Action When High Low limit range alarm is selected in A4 ...

Страница 29: ...z 24 V AC DC 50 60Hz Allowable voltage fluctuation range 85 to 264 V AC 20 to 28 V AC DC General Structure Dimensions 96 x 48 x 100 mm W x H x D Mounting Flush Mountable panel thickness 1 to 8 mm Material Case Flame resistant resin Color Light gray Drip proof Dust proof IP66 for front panel only Setting method Input system using membrane sheet key Display PV Display Red LED 5 digits Character size...

Страница 30: ...tatus will be maintained until the following is conducted The FAST key is pressed for approx 3 seconds The power is turned OFF The HOLD is cancelled by the Event input function During Alarm HOLD corresponding alarm action indicator flashes Output Relay contact 1a Control capacity 3 A 250 V AC resistive load Electrical life 100 000 cycles Transmission output 1 Converting the PV to analog signal eve...

Страница 31: ...red value has dropped below indication range low limit Thermocouple RTD input Input Input Range Indication Range K 200 to 1370 250 to 1420 320 to 2500 420 to 2600 200 0 to 400 0 200 0 to 450 0 200 0 to 750 0 200 0 to 850 0 J 200 to 1000 250 to 1050 320 to 1800 420 to 1900 R 0 to 1760 50 to 1810 0 to 3200 100 to 3300 S 0 to 1760 50 to 1810 0 to 3200 100 to 3300 B 0 to 1820 50 to 1870 0 to 3300 100 ...

Страница 32: ...from 3 types of HOLD function and 2 types of Alarm HOLD function Not available if Serial communication C5 option is ordered HOLD PV indicated value only at the given time is held and indicated by closing Event input terminals 14 17 The HOLD function is cancelled by opening Event input terminals 14 17 Peak HOLD The updated maximum PV is indicated by closing Event input terminals 14 17 The Peak HOLD...

Страница 33: ...A RS 485 Communication method Half duplex communication Communication speed 2400 4800 9600 19200 38400 bps Synchronization method Start stop synchronization Parity Even Odd No parity Selectable by keypad Stop bit 1 2 Selectable by keypad Communication protocol Shinko protocol Modbus ASCII Modbus RTU In addition each protocol above is available with Block read Selectable by keypad Connectable numbe...

Страница 34: ... 30 mA Ripple voltage Within 200 mV DC When load current is 30 mA Max load current 30 mA DC Transmission output 2 T 2 option This option cannot be used with Alarm 4 output A4 option together Resolution 12000 Output accuracy Within 0 3 of transmission output span Response time 400 ms Input sampling period 0 90 Option Code Transmission Output Type TA2 4 20 Direct current 4 to 20 mA DC Load resistanc...

Страница 35: ...may be disconnected Check whether the input terminals of thermocouple RTD or DC voltage 0 to 1 V DC are securely connected to the instrument input terminals Connect the sensor terminals to the instrument input terminals securely The PV Display flashes Check whether input signal wire for DC voltage 1 to 5 V DC or direct current 4 to 20 mA DC is disconnected How to check whether the input signal wir...

Страница 36: ... 5 V DC 0 to 10 V DC or direct current 0 to 20 mA DC are securely connected to the instrument input terminals Connect the input terminals of DC voltage and current to the input terminals of this instrument securely The indication of PV Display is irregular or unstable Check whether sensor input or temperature unit or is correct Select the sensor input and temperature unit or correctly Sensor corre...

Страница 37: ...high limit 1 Low limit alarm Input range low limit to input range high limit 1 High limit with standby alarm Input range low limit to input range high limit 1 Low limit with standby alarm Input range low limit to input range high limit 1 High Low limit range alarm A4 A4 low limit value Input range low limit 2 to A4 high limit A4 high limit value A4 low limit to input range high limit 3 The placeme...

Страница 38: ...d in the non volatile IC memory Do not change any setting items in Auxiliary function setting mode 2 pp 18 24 If any item is changed in Auxiliary function setting mode 2 it will affect the alarm value A1 value A4 value Sensor correction coefficient Setting range 10 000 to 10 000 Sensor correction Setting range 1000 0 to 1000 0 Direct current DC voltage input 10000 to 10000 The placement of the dec...

Страница 39: ... to 900 0 Pt100 200 to 850 Pt100 300 to 1500 JPt100 200 to 500 JPt100 300 to 900 4 20 mA DC 2000 to 10000 Externally mounted 50 shunt resistor 0 20 mA DC 2000 to 10000 Externally mounted 50 shunt resistor 0 1 V DC 2000 to 10000 0 5 V DC 2000 to 10000 1 5 V DC 2000 to 10000 0 10 V DC 2000 to 10000 4 20 mA DC 2000 to 10000 Built in 50 shunt resistor 0 20 mA DC 2000 to 10000 Built in 50 shunt resisto...

Страница 40: ...h standby alarm High Low limit range alarm A1 Energized De energized Energized De energized A2 Energized De energized Energized De energized A3 Energized De energized Energized De energized A4 Energized De energized Energized De energized A1 hysteresis Setting range 0 1 to 100 0 Direct current DC voltage input 1 to 1000 A2 hysteresis Setting range 0 1 to 100 0 Direct current DC voltage input 1 to ...

Страница 41: ...PV is indicated by closing Event input terminals 14 17 The Peak HOLD function is cancelled by opening Event input terminals 14 17 Bottom HOLD The updated minimum PV is indicated by closing Event input terminals 14 17 The Bottom HOLD function is cancelled by opening Event input terminals 14 17 Alarm HOLD 1 If any of A1 HOLD function to A4 HOLD function is set to Enabled and if the alarm is ON the a...

Страница 42: ...enance mode press the UP and FAST keys in that order together for approx 5 seconds in PV SV Display Mode If the unit enters Maintenance mode all outputs are forced to turn OFF Characters Factory Default Setting Item Function A1 output ON OFF Output OFF Output ON A2 output ON OFF Output OFF Output ON A3 output ON OFF Output OFF Output ON A4 output ON OFF Output OFF Output ON Transmission output 1 m...

Страница 43: ...BLUF VBLUF VBLUF VBLUF VBLUF JS EJSPLBYFE VBLUF VBLUF JS EJSPLBYFE VBLUF VBLUF JS EJSPLBYFE 1JSPLBY 7OEF 5 6 371 68 IJHI LJMJT VBLUF FT VBLUF LODK FNSOR DORRFD TJON DOFGGJDJFNT FNSOR DORRFDTJON 0OMMUNJDBTJON PROTODOL 353 0 7 387 371 68 5NSTRUMFNT NUMCFR 0OMMUNJDBTJON SPFFE BRJTY FTURNS TO 1JSPLBY 7OEF FTURNS TO 1JSPLBY 7OEF TOP CJT 353 0 7 387 371 68 DBLJNH IJHI LJMJT DBLJNH LOW LJMJT 1FDJMBL POJN...

Страница 44: ...M Serial number No 165F05000 In addition to the above please let us know the details of the malfunction or discrepancy and the operating conditions No JIR32E2 2018 02 SHINKO TECHNOS CO LTD OVERSEAS DIVISION Head Office URL E mail 2 5 1 Senbahigashi Minoo Osaka Japan http www shinko technos co jp e overseas shinko technos co jp Tel Fax 81 72 727 6100 81 72 727 7006 ...