9
3. Mounting to the Control Panel
3.1 Site Selection
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122 ) that does not
change rapidly
• An ambient non-condensing humidity of 35 to 85 %RH
• No large capacity electromagnetic switches or cables through which large current is flowing
• No water, oil or chemicals or where the vapors of these substances can come into direct contact
with the unit
• Please note that the ambient temperature of this unit – not the ambient temperature of the control
panel – must not exceed 50
(122 ) if mounted through the face of a control panel, otherwise the
life of electronic components (especially electrolytic capacitors) may be shortened.
3.2 External Dimensions
(Scale: mm)
(Fig. 3.2-1)
3.3 Panel Cutout
(Scale: mm)
Vertical close mounting
n: Number of mounted units
Caution: If vertical close mounting is
used for the instrument, IP66 (Drip-proof/
Dust-proof) may be compromised, and all
warranties will be invalidated.
(Fig. 3.3-1)
Gasket
Terminal cover
4
8
4
4
.5
2
(*
)
11.5
98.5
104.5(*)
96
106.2
(*) When terminal cover is used
130
92
+0.8
0
n
×
4
8
-
3
+
0
.
5
0
92
+0.8
0
4
5
+
0
.
5
0