9-3. Stopping Operation
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after
stopping the engine as they are still extremely hot.
(1) Manual Start
Turn the switches and breakers on the load side to OFF position.
Turn off the main breaker on the operation panel of this machine.
Confirm that the "ACCESSORY" switch is set to OFF position.
The engine cools down for approximately 3 minutes.
Turn the starter switch to STOP position.
After engine stops, turn the fuel levers to CLOSE.
<
Note >
Never turn accessory switch ON during operation.The engine keeps running while accessory
switch is ON.
If the engine does not stop even if the STARTER SWITCH is set to STOP, close the fuel
levers.The engine will stop after a few minutes. If this occurs, stop using the generator and
request authorized distributor to repair where this generator was purchased.
Set the STARTER SWITCH selector to STOP position if the generator will not be used for a
prolonged period. If you leave the selector in the AUTO or START position, the standby current
may drain the battery.
(2) Auto Start
The engine stops when the REMOTE START terminal opens.
Set the STARTER SWITCH selector to STOP position, and close the fuel levers if the generator
may not be used may not be used for a prolonged period.
<
Note >
Never turn accessory switch ON during operation.The engine keeps running while accessory
switch is ON.
Close the fuel levers if the engine does not stop when the REMOTE START terminal opens. The
engine will stop after a few minutes. If this occurs, stop using the generator and request
authorized distributor to repair where this generator was purchased.
Set the STARTER SWITCH selector to STOP position if the generator may not be used for a
prolonged period. If you leave the selector in the "AUTO" or START position, the standby current
may drain the battery.
9-4. Protective Functions
WARNING : INJURY
Do not open the check door when the starter switch is in the AUTO or START
position. It will cause injury by rotating parts such as cooling fans and fan belt.
Always turn the starter switch to the STOP position and stop the engine,
then close and lock OPERATION PANEL DOOR before checking or
maintaining the engine or any equipment.