(2) 1-Phase Output Terminals and Receptacle
For 1-phase load
The terminal Voltage: 100V/110V at 50Hz/60Hz only.
In the case of no use of 3-Phase output power, refer to the Following drawing and
chart
Voltage 100V/110V only
Unit
U1-U0
W1-W0
CON1
CON2
Sub Total
Total
kVA
10 / 11
[5 / 5.5]
10 / 11
[5 / 5.5]
1.5/1.65
[1.5/1.65]
1.5/1.65
[1.5/1.65]
10 / 11
[5 / 5.5]
20 / 22
[10 / 11]
kW
10 / 11
[5 / 5.5]
10 / 11
[5 / 5.5]
1.5/1.65
[1.5/1.65]
1.5/1.65
[1.5/1.65]
10 / 11
[5 / 5.5]
20 / 22
[10 / 11]
* Figures in brackets are used when set to 400/440 V.
< Note >
If using a 1-phase 100/110 V (between output terminals U1-UO and W1-WO), connect an
equivalent load between U1-UO and W1-UO
If using a 1-phase output terminal simultaneously with a receptacle output, make sure that
currents passing through R phase is less than the rated current of this generator.
Alternator assembly burnout can occur due to generated heat if the load current exceeds the
allowable current limit,especially when 3-phase voltage has been set to 400/440V.
CON1
CON2
U1-U0
W1-W0
U1 U0
W1 W0
Sub Total
Total