- 7 -
6. Terminal arrangement and wiring example
R
U
㻾㼍㼜㼕㼐㻌㼒㼡㼟㼑
䈜
䈜
䈜㻌㼃㼕㼞㼑㻌㼟㼛㻌㼠㼔㼍㼠㻌㼠㼔㼑㻌㻾㻌㼠㼑㼞㼙㼕㼚㼍㼘㻌㼛㼒㻌㼠㼔㼑㻌㼙㼍㼕㼚㻌㼏㼕㼞㼏㼡㼕㼠㻌㻔㼜㼛㼣㼑㼞㻌㼟㼡㼜㼜㼘㼥㻌㼒㼛㼞㻌㼘㼛㼍㼐㻕㻌㼍㼚㼐㻌㻾㼍㻌㼠㼑㼞㼙㼕㼚㼍㼘㻌㼛㼒㻌
㻌㻌㻌㻌㻌㼠㼔㼑㻌㼏㼛㼚㼠㼞㼛㼘㻌㼏㼕㼞㼏㼡㼕㼠㻌㼔㼍㼢㼑㻌㼠㼔㼑㻌㼟㼍㼙㼑㻌㼜㼔㼍㼟㼑㻚
100 - 240V
Main power supply
External
adjuster
Control
input
1
2
3
4
5
6
7
8
9
10
11
12 Ta
Ra
AL1
AL2
C1
C2
C3
R1
R2
R3
L2
M2
Control input
terminal
Main power supply / load
R
㸸
Power supply
terminal
U
㸸
Output terminal
[80/100A Terminal]
R
U
[45/60A Terminal]
R
U
[
20/30A Terminal
]
R
U
Screw diameter:
2-M8
Screw diameter:
2-M5
Screw diameter:
2-M4
Control power
supply input
Load
7. Power supply and load wiring
7-1. Wiring
Wire while referring to the figure above. If using a rapid fuse, place at entrance to main power supply (R terminal).
Remove the terminal block cover to connect wires to the terminal block.
Loosen the fastening screws mounted on the device and wire.
7-2. Power supply and load wiring
PAC18A employs 2-terminal wiring. M4 screws are used for the R and U terminals of 20/30A, M5 for 45/60A and M8 for 80/100A.
Use the proper terminal and securely fasten the screws.
䃅 㻰
Use wiring of material that matches current capacity for R and U terminals.
Current capacity
20A/30A
45A/60A
80A/100A
Φ
(mm)
Min. 4
Min. 5
Min. 8
D (mm)
Max. 10
Max. 13
Max. 14
Screws
M4
M5
M8
Fastening
torque (N·m)
1.2
㸫
1.4
2.0
㸫
2.4
5.5
㸫
6.6