4. Setup location
The device is designed to be used under the following conditions. Observe the following environmental conditions when using:
1) Indoor use
2) Elevation: Max. 2000 m (see ‘1
5-2. Ambient temperature, elevation
and load current.’)
3) Temperature range: -
10 − 55°C (see ‘1
5-2. Ambient temperature, elevation
and load current.’)
4) Humidity range: Max. 90% RH Must be no dew condensation.
5) Overvoltage category: II
6) Pollution class: 2 (IEC 60664)
CAUTION
Do not use in the following locations. Doing so could lead to equipment failure, damage or fire.
• Places exposed to flammable or corrosive gases, o
il mist, or excessive dust that could cause insulation to deteriorate
• Places subject to vibration or impact
• Places exposed to water dripping or direct sunlight
• Places directl
y exposed to air from heater or air conditioner
• Places where maintenance c
annot be performed safely
5. Mounting
Fasten to control panel, wall, rack, etc., when using. To ensure safety, arrange so that people cannot easily come into contact with the equipment.
Be sure to mount vertically to allow heat to dissipate. Provide at least 100 mm of clearance above and below the device.
If the device has to be mounted horizontally, operate at no higher than 50% of the current capacity.
5-1. Mounting method and clearance
Provide the clearance shown in the figure.
䠬䠝䠟䠍䠔
A
䠬䠝䠟䠍䠔
A
䠬䠝䠟䠍䠔
A
Min. 20mm
Min. 20mm
Min. 100mm
Min. 100mm
CAUTION
Be careful not to damage the cable by touching the heat sink or pinching the wires.
In some cases, doing so could result in fire.
Use a cable that is capable of withstanding at least 105°C.