-24-
2. Initial setting screen group
Group of screens for setting operation conditions for the device.
Must be set in advance.
The initial setting screen group is accessed by pressing and holding
for at least 1.5 seconds from key sequence ‘0-0. Output monitor (basic
screen).’ Output is forced off (output OFF).
To escape for the initial setting screen, press and hold
for at least 1.5
seconds from key sequence ‘2-0. Initial screen.’ Switches to monitor
screen group.
Switches parameters.
Enters selection.
2-0. Initial screen
Initial screen for initial setting screen group.
Switch to this screen when returning to the basic screen.
Switches to subsequent screen
→
key sequence ‘2-1.’
Pressing 1.5 seconds switches to monitor screen group
→
key sequence ‘0-0.’
2-1. Control input type selection
Selects type of control input for the device.
Initial value:
:
Voltage/current control input
:
Contact 2-position control input
Entered by
2-2. Software version display
Displays software version of the device.
V1.00 is shown in this display.
2-3. Parameter initialize
Resets initial settings screen group and user parameter group to factory settings.
Executed by
. (Restart after executing reset.)
Initial value:
:
Initialize
:
No initialize
Entered by
2-4. Power supply instantaneous stop handling function
(effective when phase control or complex control is selected)
Sets slow-up operation when power is restored after instantaneous power
stop is detected.
Initial value:
:
Slow-up conducted
:
Slow-up not conducted
Entered by
Switches to key sequence ‘2-0. Initial screen.’
3. Manual output screen group
To conduct manual output by key operation, open the connection between
C2 and C3 terminals. (You cannot switch to this screen if the terminals are
shorted.)
When communication manual output operation be enabled, the manual
output screen group can not be selected by key operation.
When Contact 2-position control input be selected, the manual output
screen group can not be selected by key operation.
With the heater break alarm function, there is an operation to measure
resistance value of the heater.
Switches parameters.
Enters selection.
3-0. Switch to manual output
Pressing and holding
for at least 1.5 seconds switches from the ‘0-0.
Output monitor (basic screen)’ to manual output.
When manual output is switched to from the key sequence ‘0-0. Output
monitor (basic screen),’ the immediately preceding control input values are
carried over.
If reverting to the key sequence ‘0-0. Output monitor (basic screen)’ from
manual output, output is in accordance with control input values at that time.
key sequence ‘0-0.’ Basic screen
Press and hold for 1.5 seconds.
displayed approx. 1 second
3-1. Manual output screen
Displays the manual output screen.
:
Displays manual output values.
Range: 0.0 – 100% (fractional digits below decimal point
not displayed for 100%)
Output is 100% for this display.
Output can be changed by
key.
key switches to resistance setting screen
.
Pressing and holding the
key for 1.5 seconds reverts
to basic screen
.
3-2. Setting of break judgment standard for heater break (optional)
Sets (loads) break judgment standard for heater break.
Set to normal state by manual output and enter the resistance value at that time.
Sets this as the judgment standard for good condition. Future deterioration
percentage is set to determine when heater break has occurred.
Deterioration value input is set by key sequence ‘1-12. Heater break alarm
current.’
:
Displays heater resistance setting screen.
(Data is stored by
.)
:
Reverts to key sequence ‘3-1. Manual output operation.’
Press and hold for 1.5 seconds.
Reverts to key sequence ‘0-0. Output monitor (basic screen).’