background image

- 35 -

Ŷ

 Analog output (option) 

Ɣ

 Number of output points 

: 1 

Ɣ

 Type of analog output    

: Selectable from measured value, target value (SV in execution) and control output 

Ɣ

 Output specification/rating 

: Current 4 - 20mA DC (Maximum load resistance 300 

Ÿ

) Voltage 0 - 10V DC (Maximum load 

    resistance 

2mA) 

10mV 

DC 

(Output 

resistance 

10 

Ÿ

)

Ɣ

 Output accuracy     

: ±0.3% FS (Comprehensive accuracy when measured value is output ±0.6% FS ) 

Ɣ

 Scaling     

: Within measuring range or output range (inversed scaling possible) 

Ɣ

 

Output 

resolution 

      : 

About 

1/10000 

Ɣ

 Output updating cycle  

: 0.25 second 

Ɣ

 Isolation    

: Not insulated from P.I.V. control output but insulated from others 

Ŷ

 Status output (DO) (option) 

Ɣ

 Number of output points   

: 4 

Ɣ

 Type of output     

: None, scaleover, hold, guarantee soak, time signal (2 types), RUN status, step signal, end signal, FIX

Ɣ

 Output specification/rating 

: Open collector darlington output, voltage 24V DC (maximum load current 20mA), saturation voltage

    during 

status 

output 

ON 

1.2V 

Ɣ

 Output updating cycle  

: 0.25 second 

Ɣ

 

Isolation 

 

   : 

Insulated 

from 

other 

inputs 

and 

outputs 

Ŷ

 Program 

Ɣ

 Number of patterns  

: Maximum 4 (setting 1, 2 or 4 possible) 

Ɣ

 Number of steps     

: Maximum 10 - 40 (Total number of steps = 40) 

Ɣ

 Number of PID types 

: Maximum 6 

Ɣ

 Number of zone PID types 

: Maximum 3 

Ɣ

 Zone hysteresis    

: 0 - 999 digits 

Ɣ

 Time setting     

: 0 hour 0 minute - 99 hours 59 minutes or 0 minute 0 second - 99 minutes 59 seconds/1 step 

Ɣ

 Setting resolution    

: 1 minute or 1 second 

Ɣ

 Accuracy of time    

: ± (set time × 0.02% + 0.25 second) 

Ɣ

 Setting for each step     

: SV, step time and PID No. 

Ɣ

 

Time 

signal   

   : 

outputs/pattern, to be set within time setting range 

Ɣ

 Number of pattern executions  : Maximum 9999 

Ɣ

 PV start   

      : ON/OFF 

Ɣ

 Guarantee soak  

: OFF, 1 - 999 digits 

Ɣ

 

Hold   

   : 

Front 

key 

input 

or 

external 

control 

input 

Ɣ

 

Advance 

 

   : 

Front 

key 

input 

or 

external 

control 

input 

Ɣ

 Power failure compensation 

: ON/OFF (guarantee not applicable to the period of time of step in which power failure occurs) 

Ŷ

 General specification 

Ɣ

 

Data 

storage 

   : 

Non-volatile 

memory 

(EEPROM) 

Ɣ

 Environmental conditions for instrument operation: 

  Temperature     : 

–10 

– 

50 

˚C

  Humidity      : 

90% 

RH 

or 

less 

(no 

dew 

condensation) 

  Height 

   : 

2000m 

from 

the 

sea 

level 

or 

lower 

    Category            : II 
  Degree 

of 

pollution 

 

Ɣ

 Storage temperature   

Ɣ

 Supply voltage    

: 2 
: –20 – 65

 

˚C

: 100 - 240V AC±10% 50/60Hz 

        24V AC/DC±10% (option) 

Ɣ

 Input/noise removal ratio 

: 50 dB or higher in normal mode (50/60 Hz) 

    130 

dB 

or 

higher 

in 

common 

mode 

(50/60 

Hz) 

Ɣ

 Insulation resistance 

: Between input/output terminals and power terminal 500V DC 20 M

Ÿ

 or above 

    Between 

input/output 

terminals 

and 

protective 

conductor 

terminal 

500 

DC 

20 

M

Ÿ

 or above 

Ɣ

 Dielectric strength 

: Between input/output terminals and power terminal 3000 V AC/minute 
 Between 

power 

terminal 

and 

protective 

conductor 

terminal 

1500V 

AC/minute 

Ɣ

 Power consumption  

: 16VA maximum for AC, 7 W for DC 

Ɣ

 Conformity with standards 

   Safety 

IEC61010-1 

and 

EN61010-1 

IEC61010-2-030 and EN61010-2-030 

   EMC : 

EN61326-1 

Ɣ

 Protective structure 

: Only front panel has dust-proof and drip-proof structure equivalent to IP66. (Panel thickness :1.2-3.2mm) 

Ɣ

 Material of case     

: PPE(equivalent to UL94V-1) 

Ɣ

 External dimensions   

: H96 × W96 × D111mm (Panel depth: 100mm) 

Ɣ

 Panel thickness    

: 1.0 - 4.0mm 

Ɣ

 Mounting dimensions  

: H92 × W92mm 

Ɣ

 

Weight  

   : 

Approximately 

450 

Содержание FP93

Страница 1: ...otice Please ensure that this instruction manual is given to the final user of the instrument Preface This instruction manual is meant for those who will be involved in the wiring installation operati...

Страница 2: ...Setting Step SV 17 2 Setting Step Time 17 3 Setting PID No 17 5 8 Explanation of screen Group 3 and Setting 17 1 Setting ON OFF of FIX Mode 17 2 Setting FIX SV Value 17 3 Setting FIX No 17 4 Setting F...

Страница 3: ...the switch or the breaker adjacently to the instrument in a position which allows it to be operated with ease with an indication that it is a means of turning the power off Use a switch or a breaker...

Страница 4: ...resistor 250 for current input 1 pc Terminal resistor 120 for RS 485 1 pc NOTE For any problem with the product shortage of accessories or request for information please contact our sales agent 2 2 Ha...

Страница 5: ...ction 3 5 and the terminal arrangement in Section 3 6 and make sure to carry out the correct wiring d Use press fit terminal which fits an M3 5 screw and has a width of 7 mm or less e In case of therm...

Страница 6: ...output Contact COM SSR drive voltage Voltage Current Contact NO SSR drive voltage Voltage Current Contact NC 14 15 16 Event output COM EV1 EV2 EV3 17 18 19 20 Analog output option 21 22 Communication...

Страница 7: ...ed as communication mode 9 AT green Auto tuning action lamp Blinks while AT is in execution The lamp lights during standby for AT and goes out when AT action comes to an end or is terminated 10 MAN gr...

Страница 8: ...essed in the middle of setting in screen groups 1 3 4 or 5 the initial screen of the group is called onto display When pressed in the screen group 2 the initial screen of screen group 1 is called onto...

Страница 9: ...oup 5 calls the basic screen of screen group 0 NOTE 3 Pressing the key in any screen group calls the next screen and pressing it on the last screen of a screen group calls the initial screen NOTE 4 A...

Страница 10: ...10...

Страница 11: ...11...

Страница 12: ...ting 5 32 Analog output type setting 5 11 PV filter setting 5 33 Analog output scaling lower limit setting 5 12 Output control characteristics setting 5 34 Analog output scaling higher limit setting 5...

Страница 13: ...group 4 calls the basic screen of screen group 0 Pressing the key on the initial screen of screen group 5 calls the basic screen of screen group 0 Pressing the key on any screen midway of screen grou...

Страница 14: ...g range codes on the 5 5 Measuring range code setting screen For current voltage or mV input lower higher limit values and the position of decimal point of the contents of display in response to input...

Страница 15: ...PROG mode If stop RST is input through external control input DI 1 or in the case of a change to FIX mode through DI the 0 0 basic screen is returned In case is set for external control input DI it f...

Страница 16: ...F Setting range OFF 1 End step A step in which TS2 signal is stopped is set This screen is not displayed when TS2 ON step is OFF A change of end step makes four decimal places blink if set value of en...

Страница 17: ...out as PID No 1 To 2 1 screen 5 8 Explanation of screen Group 3 and Setting 3 0 Initial screen To 4 0 screen representing FIX mode is shown on PTN display 1 Setting ON OFF of FIX Mode 3 1 FIX mode ON...

Страница 18: ...PID does not function and ordinary PID action is carried out This screen is not displayed when P OFF 4 7 Lower limit output limiter setting screen To 4 1 PID No 1 screen To 4 10 zone PID screen Initia...

Страница 19: ...it of measuring range is displayed and no change is possible A set value is unable to be changed during RUN in the PROG mode To 5 8 screen 5 8 Input scaling higher limit value setting screen To 5 0 sc...

Страница 20: ...5 19 Event 1 EV1 type setting screen To 5 0 screen Initial value Setting range The type of event to be set as EV1 is selected from the following table To 5 20 screen Table of Event Type Codes Code Typ...

Страница 21: ...n To 5 0 screen Initial value The higher limit value of setting range for PV and SV and 100 0 for OUT Setting range Within measuring range when PV or SV is selected and 0 0 100 0 when OUT is selected...

Страница 22: ...M LOC COM LOC Keyoperation Available Available Notavailable Available Communicationwriting Available Available Available Notavailable 18 Setting Keylock 5 45 Keylock setting screen To 5 0 screen Initi...

Страница 23: ...o manual output is not possible while auto tuning is in execution 100 output is shown as and the decimal point of blinks When OFF is set for proportional band P in the case of contact output or SSR dr...

Страница 24: ...unction to correct an offset constant deviation produced in proportional band The longer the integral time the weaker the correcting action that is reducing the integral time strengthens the correctin...

Страница 25: ...by shorting across terminals 1 and 2 ADV As on the 0 6 ADV execution screen when executed the present step comes to an end and is forced to proceed to the next step Being edge input ADV is executed ev...

Страница 26: ...g screen When event output is used as an alarm select from 1 2 and 3 of the standby action code table When event output is used for control set 4 control mode In case 4 is selected however event outpu...

Страница 27: ...HLD the change is not reflected until HLD is released Reasons why time signal does not function always OFF Time signal does not function in the following cases 1 or is not set as status output of eve...

Страница 28: ...r Break of thermocouple input wiring Break of R T D input A wiring Input measured value exceeded higher limit of measuring range by more than 10 Check thermocouple input wiring If wiring has no proble...

Страница 29: ...alue includes action type E1 i Hd 2000 digit Ld 1999 digit od 2000 digit id 2000 digit HA Higher limit of measuring range LA Lower limit of measuring range 1 12 EV2 level value includes action type E2...

Страница 30: ...ID hysteresis dF 20 digit 4 3 PID I I ijh 4 4 PID D d kh 4 5 PID MR mr rh 4 6 PID SF SF rlh 4 7 PID lower limit o_L rh 4 8 PID higher limit o_H ihrh PID No 5 4 0 Initial screen Pid 4 1 PID P P uh 4 2...

Страница 31: ...External control input 4 code di4c l 5 19 EV1 action type E1_m i 5 20 EV1 hysteresis E1_d i 5 digit 5 21 EV1 standby setting E1_i i i 5 22 EV2 action type E2_m j 5 23 EV2 hysteresis E2_d j 5 digit 5...

Страница 32: ...setting EV3 setting 20 The number of pattern executions 10 Guarantee soak PV start 0 Step No 1 2 3 4 5 6 7 8 9 10 SV set value Time PID No 0 6 Copy these pages for your use as occasion demands Zone PI...

Страница 33: ...rent mA Thermocouple Input impedance 500 k minimum External resistance tolerance 100 maximum Influence of lead wire tolerance 1 2 V 10 Burnout function standard up scale Cold junction compensation acc...

Страница 34: ...igits Within higher lower limit deviations 0 2000 digits Standby action Selectable from the following 4 types respectively for EV1 EV2 and EV3 None Standby 1 standby only when power is applied Standby...

Страница 35: ...nd PID No Time signal 2 outputs pattern to be set within time setting range Number of pattern executions Maximum 9999 PV start ON OFF Guarantee soak OFF 1 999 digits Hold Front key input or external c...

Страница 36: ...36 PRINTED IN JAPAN...

Отзывы: