background image

16

www.shieldglobal.com

MODEL: SD2133, SD2121

DESCRIPTION

The SD2133, SD2121,

½

” ori ce, standard vertical sidewall

 

sprinkler is designed for standard installation. The design

 

provides  a  crescent-shaped  water  discharge  pattern  for  

installation along a wall or under a beam or ceiling. The design

 

incorporates  state-of-the-art,  heat  responsive,  frangible  glass 

bulb design (standard or quick response) for prompt, precise

 

operation. The die cast frame is more streamlined and attractive
than traditional sand cast frames.

It is cast with a hex-shaped wrench boss to allow easy tightening
from many angles, reducing assembly effort. This sprinkler is
available in various temperature ratings and nishes to meet
many design requirements. The recessed pendent should be

 

utilized with a recessed escutcheon which provides up

”  of  

adjustments. All sprinklers are manufactured using the time

 

proven Belleville seal used exclusively by all major manufactures
to ensure long life and safe operation.

SPRINKLER OPERATION

The operating mechanism is a frangible glass bulb which contains
a heat responsive liquid. During a re, the ambient temperature
rises causing the liquid in the bulb to expand.

When  the  ambient  temperature  reaches  the  rated  temperature 

of the sprinkler, the bulb shatters. As a result, the waterway is

cleared of all  sealing parts and water is discharged towards the 

de ector. The de ector is designed to distribute the water in a
pattern that is most effective in controlling the re.

MAXIMUM COVERAGE

Standard spray coverage is up to:Light Hazard = 196
square feet(18,2 sq.m); Ordinary Hazard = 100 square
feet(9,3 sq.m)per NFPA 13.

TECHNICAL SPECIFICATION

RATINGS

SPRINKLER HEAD

Vertical Sidewall Sprinkler

Sprinkler Identi cation

Number

Standard SD2133 (bulb 

5mm), Quick Response
SD2121 (bulb 3mm)

Style

Vertical Sidewall

K Factor

5.6gpm/psi

½

. (80lpm/bar

½

)

Response Time Index
(RTI)

Standard 50
Quick Response 30

Nominal Thread Size

½

”NPT(15mm)

Or ce Size

13mm

Max. Working Pressure 175PSI(1200kPa)

Factory Hydrostatic Test 100%@500PSI(3450 kPa)

Min. Operation Pressure 7 PSI(48 kPa)

Sprinkler Temperature

Classi cation

Norminal Sprinkler

Temperature Rating

N.F.P.A Maximum Ambient

(Ceiling) Temp.(Allowed)

Glass Bulb Color

Ordinary

135ºF/57ºC

100ºF/38ºC

Orange

Ordinary

155ºF/68ºC

100ºF/38ºC

Red

Intermediate

175ºF/79ºC

150ºF/65ºC

Yellow

Intermediate

200ºF/93ºC

150ºF/65ºC

Green

Содержание SD1010

Страница 1: ...rature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 225 square feet 20 9 sq m Ordinary Hazard 130 square feet 12 1 sq m per NFPA 13 TECHNI...

Страница 2: ...7 www shieldglobal com PART LIST DISCHARGE CURVE SD1015 SD1010 SD1030 SD1032 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb ...

Страница 3: ...and push or thread over the sprinkler body into the upper support piece until the outer edge of the escutcheon meets the mounting surface INSTALLATION SEQUENCE Step 1 The unit must be installed in the upright position for the Upright Sprinklers and in the Pendent position for the Pendent Sprinkler Pendent Recessed Sprinkler Step 2 Use only a non hardening pipe joint compound or tape seal Apply onl...

Страница 4: ...9 www shieldglobal com DISTRIBUTION PATTERNS K5 6 PENDENT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY K5 6 UPRIGHT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY ...

Страница 5: ...10 www shieldglobal com DIMENSIONS UPRIGHT SPRINKLER PENDENT SPRINKLER RECESSED PENDENT SPRINKLER Maximum Extension Maximum Recess ...

Страница 6: ... the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 196 square feet 18 2 sq m Ordinary Hazard 100 square feet 9 3 sq m per...

Страница 7: ...12 www shieldglobal com PART LIST SD1133 SD1121 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Страница 8: ...escutcheon plate align with it and push or thread over the sprinkler body into the upper support piece until the outer edge of the escutcheon meets the mounting surface INSTALLATION SEQUENCE Step 1 The unit must be installed in the horizontal sidewall position for the Horizontal Sidewall Sprinklers Step 2 Use only a non hardening pipe joint compound or tape seal Apply only to the male threads Step...

Страница 9: ...w shieldglobal com DISTRIBUTION PATTERNS K5 6 STANDARD HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS TRAJECTORY K5 6 STANDARD HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS PLAN VIEW ...

Страница 10: ...15 www shieldglobal com DIMENSIONS RECESSED PENDENT SPRINKLER Maximum Extension Maximum Recess ...

Страница 11: ...onsive liquid During a re the ambient temperature rises causing the liquid in the bulb to expand When the ambient temperature reaches the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re ...

Страница 12: ...17 www shieldglobal com PART LIST SD2133 SD2121 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Страница 13: ...cheon plate align with it and push or thread over the sprinkler body into the upper support piece until the outer edge of the escutcheon meets the mounting surface INSTALLATION SEQUENCE Step 1 The unit must be installed in the horizontal sidewall position for the Horizontal Sidewall Sprinklers Step 2 Use only a non hardening pipe joint compound or tape seal Apply only to the male threads Step 3 Ha...

Страница 14: ...19 www shieldglobal com DISTRIBUTION PATTERNS K5 6 STANDARD VERTICAL SIDEWALL DISTRIBUTION PATTERNS TRAJECTORY K5 6 STANDARD VERTICAL SIDEWALL DISTRIBUTION PATTERNS PLAN VIEW ...

Страница 15: ...20 www shieldglobal com DIMENSIONS ...

Страница 16: ...reaches the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 225 square feet 20 9 sq m Ordinary Hazard 130 square feet 12 1 ...

Страница 17: ...22 www shieldglobal com PART LIST SD1050 SD1055 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Страница 18: ...e sprinkler and slowly turn clockwise for the cover plates and sprinkler to lock in Make sure the cover plate is securely locked in fail to do so may cause the sprinkler to malfunction INSTALLATION SEQUENCE Step 1 The unit must be installed in the Pendent position for the Concealed Sprinkler Step 2 Use only a non hardening pipe joint compound or tape seal Apply only to the male threads Step 3 Hand...

Страница 19: ...24 www shieldglobal com DISTRIBUTION PATTERNS K5 6 PENDENT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY DIMENSIONS ...

Страница 20: ...he liquid in the bulb to expand When the ambient temperature reaches the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 22...

Страница 21: ...26 www shieldglobal com PART LIST SD1021 SD1020 FRAME AND DEFLECTOR FINISH Pendent Brass Chrome White Upright Brass only 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Страница 22: ...27 www shieldglobal com DISTRIBUTION PATTERNS K4 2 PENDENT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY K4 2 UPRIGHT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY ...

Страница 23: ...28 www shieldglobal com DIMENSIONS RECESSED PENDENT SPRINKLER PENDENT SPRINKLER UPRIGHT SPRINKLER Maximum Extension Maximum Recess ...

Страница 24: ...he ambient temperature reaches the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 229 square feet 20 9 sq m Ordinary Hazar...

Страница 25: ...30 www shieldglobal com PART LIST SD1026 SD1025 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Страница 26: ...h it and push or thread over the sprinkler body into the upper support piece until the outer edge of the escutcheon meets the mounting surface INSTALLATION SEQUENCE Step 1 The unit must be installed in the upright position for the Upright Sprinklers and in the Pendent position for the Pendent Sprinkler Pendent Recessed Sprinkler Step 2 Use only a non hardening pipe joint compouind or tape seal App...

Страница 27: ...32 www shieldglobal com DISTRIBUTION PATTERNS K5 6 CONVENTIONAL SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY K5 6 CONVENTIONAL SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY ...

Страница 28: ...33 www shieldglobal com DIMENSIONS STANDARD CONVENTIONAL SPRINKLER RECESSED CONVENTIONAL SPRINKLER Maximum Extension Maximum Recess ...

Страница 29: ...cheon Plate Double pieces Bright Chrome Finish Painted available upon request Suitable for 1 2 and 3 4 Sprinkler Head HINGED ESCUTECHEONS PLATE FOR PIPE Escutecheon Plate Hinged Bright Chrome Finish Different sizes 1 2 upto 6 SPRINKLER GUARD Steel Nickel Chrome plated Suitable for 1 2 and 3 4 Sprinkler Head SPRINKLER CABINETS Steel painted Red Suitable for 1 2 Sprinkler Head Available for 6 12 24 ...

Отзывы: