11
www.shieldglobal.com
MODEL: SD1133, SD1121
DESCRIPTION
The SD1133, SD1121,
½
” ori ce, standard horizontal sidewall
sprinkler is designed for standard or recessed installation. The
design provides a crescent-shaped water discharge pattern for
installation along a wall or under a beam or ceiling. The design
incorporates state-of-the-art, heat responsive, frangible glass
bulb design (standard or quick response) for prompt, precise
operation. The die cast frame is more streamlined and attractive
than traditional sand cast frames.
It is cast with a hex-shaped wrench boss to allow easy tightening
from many angles, reducing assembly effort. This sprinkler is
available in various temperature ratings and nishes to meet
many design requirements. The recessed pendent should be
utilized with a recessed escutcheon which provides up
” of
adjustments.
SPRINKLER OPERATION
The operating mechanism is a frangible glass bulb which contains
a heat responsive liquid. During a re, the ambient temperature
rises causing the liquid in the bulb to expand.
When the ambient temperature reaches the rated temperature of
the sprinkler, the bulb shatters. As a result, the waterway is cleared
of all sealing parts and water is discharged towards the de ector.
The de ector is designed to distribute the water in a pattern that is
most effective in controlling the re.
MAXIMUM COVERAGE
Standard spray coverage is up to: Light Hazard = 196 square
feet(18,2 sq.m); Ordinary Hazard = 100 square feet(9,3 sq.m)per
NFPA 13.
TECHNICAL SPECIFICATION
SPRINKLER HEAD
Horizontal Sidewall Sprinkler
Sprinkler Identi cation
Number
Standard SD1133 (bulb
5mm), Quick Response
SD1121 (bulb 3mm)
Style
Horizontal Sidewall
K Factor
5.6gpm/psi
½
. (80lpm/bar
½
)
Response Time Index
(RTI)
Standard 50
Quick Response 30
Nominal Thread Size
½
”NPT(15mm)
Or ce Size
13mm
Max. Working Pressure 175PSI(1200kPa)
Factory Hydrostatic Test 100%@500PSI(3450 kPa)
Min. Operation Pressure 7 PSI(48 kPa)
RATINGS
Sprinkler Temperature
Classi cation
Norminal Sprinkler
Temperature Rating
N.F.P.A Maximum Ambient
(Ceiling) Temp.(Allowed)
Glass Bulb Color
Ordinary
155ºF/57ºC
100ºF/38ºC
Orange
Ordinary
155ºF/68ºC
100ºF/38ºC
Red
Intermediate**
175ºF/79ºC
150ºF/65ºC
Yellow
Intermediate**
200ºF/93ºC
150ºF/65ºC
Green
High*
286ºF/141ºC
225ºF/107ºC
Blue
Extra High*
360ºF/182ºC
300ºF/149ºC
Mauve
Open*
Open
-
No Bulb
* Non-Approved
** FM Approved only