background image

Ver. 2.0U Dec. 4, 2008 

 

 

- 3 -                                                                    Installation Manual for PV modules 

typically face south, and in the southern hemisphere, PV modules 

should typically face north. 

Please make sure that there are no obstructions in the surroundings of 

the site of installation. Take proper steps in order to maintain reliability 
and safety in case the PV modules are installed in areas that have 

heavy snow / extreme cold / strong winds / installations over, or near, 

water and areas where installations are prone to salt water exposure or 

on small islands or in desert areas. If you are planning to use the PV 

modules where salt water damage may occur, please consult with 

SHARP to determine an appropriate installation method, or if 

installation is possible. 

 
A-5. TILT ANGLE SELECTION 

The tilt angle of the PV module is measured between the surface of the 

PV module and a horizontal ground surface. The PV module generates 

maximum output power when it faces the sun directly. 

For standalone systems with batteries where the PV modules are 

attached to a permanent structure, the tilt angle of the PV modules 

should be selected to optimize the performance based on seasonal 

load and sunlight. In general, if the PV output is adequate when 

irradiance is low (e.g., winter), then the angle chosen should be 

adequate during the rest of the year. For grid-connected installations 

where the PV modules are attached to a permanent structure, PV 

modules should be tilted so that the energy production from the PV 
modules will be maximized on an annual basis. 

 

A-6. ELECTRICAL INSTALLATION

 

To ensure proper system operation and maintain the warranty, be 

careful to observe the correct cable connection polarity (Figure 1) when 

connecting the modules to a battery or to other modules. If not 
connected correctly, the bypass diode(s) could be destroyed. All PV 

modules must be grounded by electrical connection of the module 

frames to ground. Care must be taken to arrange the system ground so 

that the removal of one module from the circuit will not interrupt the 
grounding of any of the other modules. For grounding, each PV module 

has a hole in the frame for either a bolt, nut and washer, a ground lug 

fastened by bolt or screw, or an appropriate screw (hardware not 

provided). Installation for wiring shall be in accordance with the NEC 

and grounding method shall comply with the NEC, article 250 and the 

relevant instructions below. In a connection of this type, the hardware 

(such as a star washer) must score the frame surface to make positive 

electrical contact with the frame. The ground wire must not be smaller 
than No.14 AWG (2.1 mm

2

), and should be sized according to the 

NEC. 

 

Hardware used must be compatible with the mounting structure 

material to avoid galvanic corrosion. If using the SHARP On-Energy 
mounting system, the module and mounting structure may utilize an 

“integrated grounding” system in which individual wire grounding of 

every module is not required. Refer to the OnEnergy System 

Installation Manual. 
If modules are installed in a readily accessible location (per NEC) 

where the circuit is operating in excess of 30 volts, nominal, maximum 

system voltage for DC or 30 volts for AC circuits, NEC requires 

installing the additional locking sleeve connector (Multi Contact 

#PV-SSH4) on the connector. Note that this sleeve is not included with 

the module. See Figure 2. 

Grounding Using Existing Ground Hole (Figure 3)   

The existing ground holes can be used with stainless steel #10-32 
bolts, #10 lock washers and #10-32 nuts. All grounding hardware must 

have a thread count of at least 32 turns per inch. These holes may be 

used to secure an outdoor-rated, tinned copper, UL listed lay in ground 

lug such as Ilsco model GBL4-DBT or equivalent. 
 

Grounding Using Existing Unused Module Mounting Hole 

(Figure 4) 

An existing otherwise unused module mounting hole can be used to 

install the same grounding hardware noted above. Do not use a 
mounting hole or hardware that is used for structurally mounting the 

module. UL 1703 prohibits the use of a bonding fastener for any 

purpose other than ground bonding. 

 
A-7. MAINTENANCE 

SHARP PV modules are designed for long life and require very little 

maintenance. If the angle of the PV module is 5 degrees or more, 
normal rainfall is usually sufficient to keep the module glass surface 

clean under most weather conditions. If dirt build-up becomes 

excessive, clean the glass surface only with a soft cloth using water. If 

cleaning the back of the module is required, take utmost care not to 

damage the back side materials. In order to ensure proper operation of 

the system, please check all wiring connections and the condition of 

the wire insulation periodically. 

 

SERIES WIRING (VOLTAGE ADDITIVE)   

PARALLEL WIRING (CURRENT ADDITIVE) 

Additional locking sleeve 

Figure 2 

Figure 1 

Lay in Ground Lug 

Figure 3 

Figure 4 

SERIES WIRING (VOLTAGE ADDITIVE)   

PARALLEL WIRING (CURRENT ADDITIVE) 

Additional locking sleeve 

Figure 2 

Figure 1 

Lay in Ground Lug 

Figure 3 

Figure 4 

Содержание ND-U230C1

Страница 1: ...thal shock whether the PV modules are connected or not 4 PV modules produce electricity when sufficient sunlight or other light source illuminates the module When modules are connected in series voltage is cumulative When modules are connected in parallel current is cumulative PV systems can produce high voltage and current which could present an increased hazard and may cause serious injury or de...

Страница 2: ...oves with padding in the palm and finger areas 14 Do not drop the PV module or allow objects to fall on the PV module 15 Do not lift the PV module by only one side The frame may bend Always use two hands to lift and carry the PV module on the long side of the frame 16 Some PV modules incorporate one or more support bars on the back of the module Do not mount or carry the PV module using the suppor...

Страница 3: ...ions below In a connection of this type the hardware such as a star washer must score the frame surface to make positive electrical contact with the frame The ground wire must not be smaller than No 14 AWG 2 1 mm2 and should be sized according to the NEC Hardware used must be compatible with the mounting structure material to avoid galvanic corrosion If using the SHARP On Energy mounting system th...

Страница 4: ...5 11 12 The modules may be mounted using clamps designed for solar modules as shown in Figures 5 Note that the clamp positions are important the clamp centerlines must be between 9 3 235 mm and 19 4 495 mm regarding ND series as shown in Figure 11 and 8 3 210mm and 18 5 470mm regarding NT NE series as shown in Figure 12 from the end of the module The module must be supported along the length of th...

Страница 5: ... s Figure 12 NT NE series Figure 9 ND series u u u u Figure 12 NT NE series Figure 9 ND series Figure 10 NT NE series 8 3 210 mm g 18 5 470 mm Figure 11 ND series 9 3 235 mm e 19 4 495 mm Figure 13 ND series 9 3 235 mm s 19 4 495 mm 8 3 210 mm u 18 5 470 mm Figure 14 NT NE series ...

Страница 6: ...m power Ipmax 7 66 A 7 54 A 7 48 A 7 25 A 7 04 A Maximum System Voltage 600 V 600 V 600 V 600 V 600 V Minimum Blocking diode 15 A 15 A 15 A 15 A 15 A Series Fuse 15 A 15 A 15 A 15 A 15 A NT 175UC1 NT 170UC1 NE 170UC1 NE 165UC1 Maximum Power Pmax 175 0 W 142 0 W 170 0 W 165 0 W Open Circuit Voltage Voc 44 4 V 43 2 V 43 2 V 43 1 V Short Circuit Current Isc 5 40 A 5 47 A 5 47 A 5 31 A Voltage at maxi...

Страница 7: ...nship and materials and Sharp agrees that for a period of one 1 year from the date of purchase by the consumer that Sharp will at its option either repair the defect or replace the defective Product or part thereof with a new or remanufactured equivalent at no charge to the purchaser for parts or labor for the period s set forth below Limited Warranty For Power The warranty period with respect to ...

Страница 8: ...improper voltage or power surges or abnormal environmental conditions such as acid rain or other pollution c the components in the construction base on which the module is mounted are defective d external corrosion mold discoloration or the like occurs e the product has been moved from its original installation f the model number or serial number of the product is altered removed or rendered illeg...

Отзывы: