background image

EN-3

Connecting wires and the ground wire

• Use a solid or stranded wire.
  Connecting Cable: AWG16 or AWG14

  Power Supply Cable: AWG12
• Use a copper wire.
• Follow local electrical codes.
• Use a double insulated cable with 600V insulation.

Valve shaft cap tightening torque

Torque

Liquid side 17.7±2.1 ft·lbf (24±3 N·m)

Gas side

22.9±2.1 ft·lbf (31±3 N·m)

Service port cap tightening torque

Torque

8.1±0.74 ft·lbf (11±1 N·m)

4     CONNECTING THE CABLE TO THE OUTDOOR UNIT

Power Supply

Cable

Connecting Cable

Power supply cable

4.7 inch(120 mm)

3.9 inch(100 mm)

Ground Wire

Ground Wire

3.9 inch(100 mm)

In case using solid wires

Stripping length: 0.7 inch (18 mm)
Be sure to make the wire hook-shaped.

In case using stranded wires

Stripping length: 0.3 inch (8mm)
For power supply cable, securely clamp a round 
terminal to each end of the stripped wire.

0.7 inch(18 mm)

Copper Wire

0.3 inch(8 mm)

Copper Wire

Round terminal

3.1 inch(80 mm)

Fig.1

Cable Cover

Gauge manifold

Compound 

gauge

Stop  valve           

(gas side)

Service port

Vacuum pump

Lo

Hi

Stop valve 

(liquid side)

hose

Hexagon wrench

Valve shaft cap

OPEN

4mm

Service port

(1) Strip the copper wires. (Fig.1)
(2) Remove the Cable Cover. (Fig.2)
(3) Attach the Conduit Connector to Expansion Valve Angle with

 

lock nut. (Fig.3)

(4) Adjust the length of Connecting Cable. Then connect it to

 

Terminal Board. (Fig.4)

(5) Insert Connecting Cable and Power Supply Cable into Cable

 

Holder by Hook. (Fig.5)

(6) Be sure that the terminal connections are as speci

fi

 ed.(Fig.6)

(7) Attach the Cable Cover with the screws. (Fig.2)
(8) Double-check that the Connecting Cable is securely in place.

Fig.2

3      AIR REMOVAL

Perform air removal using a vacuum pump.

Use a vacuum pump, gauge manifold and hoses exclusively for R410A.

(1)  Remove both valve shaft caps of the stop valves.
(2)  Remove the service port cap of the stop valve (gas side).
(3)  Connect the gauge manifold hose to the service port and the vacuum pump.

 

Be sure that the hose end to be connected to the service port has a valve 

core pusher.

(4)  Open the gauge manifold valve and turn on the vacuum pump for 10-15 

minutes.

 

Make sure the compound gauge reads -0.1 MPa(-76 cmHg)(-30 in. Hg). 

(5)  Close the gauge manifold valve. 
(6)  Turn off the vacuum pump.

 

Leave as it off for 1-2 minutes and make sure the needle of the compound 

gauge does not go back.

(7)  Open the stop valve (liquid side) 90° counterclockwise by turning the 

hexagon wrench. Close it after 5 second, and check for gas leakage.*

(8)  Disconnect the gauge manifold hose from the service port.
(9)  Fully open the stop valve (liquid side) with hexagon wrench. 

 

Turn all the way up to contact.

(10)  Fully open the stop valve (gas side) with hexagon wrench. Turn all the way 

up to contact.

(11)  Firmly tighten the service port cap and both valve shaft caps with a torque 

wrench at the speci

fi

 ed tightening torque.   

* Check the pipe connections for gas leak using a leakage detector or soapy 

water. Regarding leakage detector, use high-sensitivity type designed specially 

for R410A.

Cable Holder

AE-X2M20RU_3_LANG.indb   EN-3

AE-X2M20RU_3_LANG.indb   EN-3

2013-12-19   21:01:19

2013-12-19   21:01:19

Содержание AE-X2M20RU

Страница 1: ...DIVIDUEL EN DEUX PARTIES MANUEL D INSTALLATION ACONDICIONADOR DE AIRE TIPO SPLIT MANUAL DE INSTALACIÓN OUTDOOR UNIT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR AE X2M20RU ENGLISH FRANÇAIS ESPAÑOL AE X2M20RU_3_LANG indb 1 AE X2M20RU_3_LANG indb 1 2013 12 19 21 01 17 2013 12 19 21 01 17 ...

Страница 2: ...nd the unit Incomplete ground may cause electrical shock Install a Gound Fault Interrupt GFI circuit breaker depending on the installation location of the unit such as highly humid areas If GFI breaker is not installed it may cause electric shock Arrange the drain hose to ensure smooth drainage Insufficient drainage may cause wetting of the room furniture etc This room air conditioner uses refrige...

Страница 3: ...for the indoor unit first and then for the outdoor unit 1 Tighten the flare nuts by hand for the first 3 4 turns 2 Use a spanner and torque wrench to tighten up the pipes Do not over tighten the pipes it may be deformed or damaged Notes Bend the pipes carefully as not to damage them Lay the drain hose below the pipes Flare nut Flaring the pipe end 1 Cutting with a pipe cutter Cut at a right angle ...

Страница 4: ...rminal connections are as specified Fig 6 7 Attach the Cable Cover with the screws Fig 2 8 Double check that the Connecting Cable is securely in place Fig 2 3 AIR REMOVAL Perform air removal using a vacuum pump Use a vacuum pump gauge manifold and hoses exclusively for R410A 1 Remove both valve shaft caps of the stop valves 2 Remove the service port cap of the stop valve gas side 3 Connect the gau...

Страница 5: ...ne or more of the LED is are kept lit check for mismatching terminal markings L1 L2 2 and correct them 3 To start the wire check press the WIRE CHECK button SW2 for 5 seconds or more The operation lamp on the indoor unit will flash and three BEEP will be emitted All LED will flash rapidly 4 When wire check is completed normally all LED will flash simultaneously and the operation will stop Wire che...

Страница 6: ... be emitted 2 After 5 10 minutes fully close the stop valve liquid side 3 After 2 3 minutes close the stop valve gas side fully 4 To stop the pump down press the PUMP DOWN button SW1 for 5 seconds or more PUMP DOWN WIRE CHECK LED1B SW1 SW2 Lo Hi Stop valve liquid side Service port Stop valve gas side Compound gauge PUMP DOMN button SW1 OFF 1 2 ON PUMP DOWN SELECT WIRE CHECK OFF 1 2 ON LED1B DSW1 S...

Страница 7: ...orrecte peut causer une électrocution Installez un disjoncteur de fuite à la terre suivant l emplacement d instal lation de l unité par exemple dans une zone très humide Si aucun disjoncteur de fuite à la terre n est installé un risque d électrocution est possible Installez le tuyau de vidange de manière à assurer un écoulement facile Un écoulement insuffisant peut provoquer l inondation de la piè...

Страница 8: ... conduites Raccordez les conduites à l unité intérieure avant de les connecter à l unité extérieure 1 Vissez manuellement l écrou évasé pour les 3 4 premiers tours 2 Utilisez une clé et une clé dynamométrique pour serrer les conduites Trop serrer les conduites risquerait de les déformer ou de les endommager Remarques Pliez les conduites prudemment afin de ne pas les abîmer Placez le tuyau de vidan...

Страница 9: ...ec les vis Fig 2 8 Vérifiez par deux fois que le câble est solidement fixé Fig 2 3 ÉVACUATION DE L AIR Évacuez l air du système avec une pompe à vide Utilisez une pompe à vide un manomètre et des tuyaux exclusivement conçus pour le R410A 1 Retirez les deux capuchons des tiges des soupapes d arrêt 2 Retirez le capuchon de l orifice de sortie de la soupape d arrêt côté gaz 3 Raccordez le flexible du...

Страница 10: ...nière continue vérifiez les marquages des câbles L1 L2 2 et corrigez 3 Pour démarrer la vérification du câblage pressez la touche de vérification du câblage WIRE CHECK SW2 pendant 5 secondes ou plus Le voyant de fonctionnement de l unité intérieure clignote puis trois bips d alarmes sont émis Tous les voyants clignotent rapidement 4 Une fois la vérification du câblage correctement terminée tous le...

Страница 11: ...re clignote puis trois bips d alarmes sont émis 2 Après 5 à 10 minutes fermez complètement la soupape d arrêt côté liquide 3 Après 2 à 3 minutes fermez complètement la soupape d arrêt côté gaz 4 Pour arrêter l évacuation pressez la touche d évacuation PUMP DOWN SW1 pendant 5 secondes ou plus PUMP DOWN WIRE CHECK LED1B SW1 SW2 Lo Hi Soupape d arrêt côté liquide Orifice de sortie Soupape d arrêt côt...

Страница 12: ...mático a tierra en función de la ubicación de la unidad por ejemplo en zonas de gran humedad Si no se instala un interruptor de corte automático a tierra podrían producirse descargas eléctricas Coloque la manguera de desagüe de forma que el líquido fluya correctamente Si el sistema de desagüe se ha instalado de forma incorrecta se pueden producir humedades en la habitación los muebles etc Este aco...

Страница 13: ...unidad exterior 1 Apriete manualmente las tuercas cónicas dándoles de 3 a 4 vueltas 2 Utilice una llave fija y una llave de torsión para apretar las tuberías No apriete demasiado las tuberías ya que pueden defor marse o dañarse Nota Doble con cuidado las tuberías para no dañarlas Coloque la manguera de desagüe debajo de las tuberías Tuerca cónica Abocardado del extremo del conducto 1 Corte con un ...

Страница 14: ...ables con tornillos Fig 2 8 Compruebe de nuevo que el cable de conexión está colocado de forma segura Fig 2 3 EXTRACCIÓN DE AIRE Extraiga el aire utilizando una bomba de vacío Utilice la bomba de vacío el manómetro y los tubos exclusivos del sistema R410A 1 Retire los dos tapones del árbol de válvulas 2 Retire el tapón del puerto de servicio de la válvula de cierre lado del gas 3 Conecte el tubo d...

Страница 15: ...erminal no coincidente L1 L2 2 y corríjalos 3 Para iniciar la comprobación de los cables pulse el botón WIRE CHECK SW2 durante al menos cinco segundos El indicador de funcionamiento de la unidad interior parpadeará y se oirán tres pitidos Todos los indicadores parpadearán rápidamente 4 Si la comprobación de cables se completa correctamente todos los indicadores parpadearán simultáneamente y la ope...

Страница 16: ...res pitidos 2 Trascurridos de 5 a 10 minutos cierre completamente la válvula de cierre lado del líquido 3 Trascurridos de 2 a 3 minutos cierre completamente la válvula de cierre lado del gas 4 Para detener el proceso de extracción pulse el botón PUMP DOWN SW1 durante al menos 5 segundos PUMP DOWN WIRE CHECK LED1B SW1 SW2 Lo Hi Válvula de cierre lado del líquido Salida de servicio Válvula de cierre...

Страница 17: ...AE X2M20RU_3_LANG indb 6 AE X2M20RU_3_LANG indb 6 2013 12 19 21 01 30 2013 12 19 21 01 30 ...

Страница 18: ...Printed in Thailand TINS B498JBRZ 14B TH 1 AE X2M20RU_3_LANG indb 7 AE X2M20RU_3_LANG indb 7 2013 12 19 21 01 30 2013 12 19 21 01 30 ...

Отзывы: