c. System Wiring, select from pull-down menu:

   - 3 Element Wye; 2.5 Element Wye; 2 CT Delta
   This value must be set properly for the meter to calculate readings correctly.

d. Use the Minimum Voltage Threshold box to enter the minimum voltage threshold, which is a 

   percentage of the voltage full scale. This setting adjusts the pick up threshold for the voltage. You
   set a percentage of the PT primary (PT numerator X PT multiplier) up to 12.7 in the entry field, to
   configure when the meter will start reading values above 0 voltage. 

e. Total Demand Distortion (TDD Setting): This setting of the Device Profile allows you to set the

   maximum value for current, which is used for the TDD (Total Demand Distortion) calculation. TDD
   is an index used to measure harmonics. In this field enter the maximum load current for TDD. To
   disable TDD, enter 0 in the field.

f. CT Reversal Phase Enables: Use this setting to enable CT reversal for any phase. This feature is

   useful if a CT is wired the wrong way and you do not want to (or cannot) change the wiring. This
   setting is only available for a three element WYE hookup. For any other hookup, this setting will
   be ignored.

Program Communications Setting:

1. From the Device Profile screen, double-click General Settings>Communications>a listed port.

    The settings shown here are for the meter’s serial ports. 
    

Содержание 250

Страница 1: ...orm lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 3 x 0 1A FUSE 3A C C B B A A N N lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 3 x 0 1A FUSE 3A C C B B A A N N lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply C...

Страница 2: ... Amps Set the Ct n value for 2000 NOTE Ct n is dictated by primary current Ct d is secondary current 6 Press the ENTER button to go to the PT numerator setting screen Pt n The current PT numerator is shown in the second line To change the setting press the DOWN ARROW until the value you want is displayed Then press the RIGHT ARROW to move to the next digit Repeat until the setting is done 7 Press ...

Страница 3: ...s the ENTER button For additional programming instructions for the faceplate buttons see Chapter 2 in the Shark 250 250T Meter Installation and Operation Manual on the enclosed CD and on EIG s website www electroind com Connect to the Meter through the USB Port The Shark 250 meter has a standard USB port that makes connection between the meter and a laptop PC very simple Follow these steps 1 Conne...

Страница 4: ...k Connect 5 The Device Status screen opens displaying information about the meter 6 Click OK to close the Device Status screen and then click the Profile icon in the Icon Bar 7 The meter s Device Profile screen opens giving you access to the programmable settings for the meter NOTE A few basic settings are explained here Refer to the Shark 250 Meter Installation and Opera tion Manual and the Commu...

Страница 5: ...items in the list to redisplay this screen a CT Ratio enter Primary CT Numerator 1 9999 Secondary CT Denominator 5 or 1 Amp b PT Ratio enter Primary PT Numerator 1 9999 Secondary PT Denominator 1 9999 Example Settings For a CT of 2000 5 A set the following CT Ratios in the entry fields CT Numerator Primary 2000 CT Denominator Secondary 5 The Current Full Scale field will read 2000 For a system tha...

Страница 6: ...eld to configure when the meter will start reading values above 0 voltage e Total Demand Distortion TDD Setting This setting of the Device Profile allows you to set the maximum value for current which is used for the TDD Total Demand Distortion calculation TDD is an index used to measure harmonics In this field enter the maximum load current for TDD To disable TDD enter 0 in the field f CT Reversa...

Страница 7: ...ore responding to queries Parity Odd Even or None Program Meter Time The meter is preset to Eastern time To change the meter time 1 From the Main screen s Title bar click Tools Set Device Time 2 You can either enter the time in the Time fields or click Use PC Time to set the time using your PC s time 3 Click Send NOTE The meter offers multiple Time Synchronization methods See Chapter 28 Section 28...

Страница 8: ...me is used to name the log databases when logs are downloaded MPORTANT When you have made changes to the meter s Device Profile click Update Device at the top left of the Device Profile screen s Icon Bar to send the new settings to the meter The meter will reboot and then you can reconnect to it Shark is a registered trademark of Electro Industries GaugeTech The distinctive shape style and overall...

Отзывы: