                      Shark® 250 Meter Quickstart

Electro 

Industries/GaugeTech

The Leader In Power Monitoring and Smart Grid Solutions

Electro 

Industries/GaugeTech

The Leader In Power Monitoring and Smart Grid Solutions

9. Press the 

ENTER 

button to go to the Scroll setting screen (SCrL). The current

    setting is shown in the second line. Press the 

DOWN ARROW

 to choose another

    setting. You can choose YES (the meter readings will scroll on the display) or no

    (the meter readings will not scroll on the display).

10.Press the 

MENU 

button twice. You will see the Store Settings screen (Stor ALL?)

     The default setting is YES. To save the settings you’ve made, press the 

ENTER

 

     button. You will see the confirmation screen (Stor ALL done) and then the meter 

     resets.

     

NOTE: 

If you do not want to save your settings, press the

 RIGHT ARROW. 

YES 

     changes to no. Press the

 ENTER 

button. 

  For additional programming instructions for the faceplate buttons, see Chapter 2 

  in the 

Shark® 250/250T Meter Installation and Operation Manual

, on the enclosed 

  CD and on EIG’s website: www.electroind.com.

Connect to the Meter through the USB Port:

The Shark® 250 meter has a standard USB port that 

makes connection between the meter and a laptop PC 

very simple.

Follow these steps:

1. Connect the meter to the PC, using the USB cable. 

    The meter’s connection uses a USB mini-B plug. For

    your convenience, EIG offers a USB-Type A plug to

    USB mini-B plug cable (part number E169305) that

    can be ordered directly from EIG’s webstore: https://electroind.com/shop/.

2. Open Communicator EXT

TM

 software (download from

    product CD). 

3. Click 

Connect

 in the Icon Bar. 

4. You will see the Connect screen. The default settings are shown in the following example screen.

0000

-
-
-

A

B

C

MENU

ENTER

-

MAX

MIN

LM1

LM2

%THD

VOLTS L-N

VOLTS L-L

AMPS

W/VAR/PF

VA/Hz

Wh

VARh

VAh

120%-

90%-

60%-

30%-

%LOAD

MEGA

KILO

Wh Pulse

PRG

A

B

C

-

-

-

MENU

ENTER

A

B

C

-

-

-

MENU

ENTER

A

B

C

-

-

-

MENU

ENTER

Содержание 250

Страница 1: ...orm lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 3 x 0 1A FUSE 3A C C B B A A N N lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 3 x 0 1A FUSE 3A C C B B A A N N lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply C...

Страница 2: ... Amps Set the Ct n value for 2000 NOTE Ct n is dictated by primary current Ct d is secondary current 6 Press the ENTER button to go to the PT numerator setting screen Pt n The current PT numerator is shown in the second line To change the setting press the DOWN ARROW until the value you want is displayed Then press the RIGHT ARROW to move to the next digit Repeat until the setting is done 7 Press ...

Страница 3: ...s the ENTER button For additional programming instructions for the faceplate buttons see Chapter 2 in the Shark 250 250T Meter Installation and Operation Manual on the enclosed CD and on EIG s website www electroind com Connect to the Meter through the USB Port The Shark 250 meter has a standard USB port that makes connection between the meter and a laptop PC very simple Follow these steps 1 Conne...

Страница 4: ...k Connect 5 The Device Status screen opens displaying information about the meter 6 Click OK to close the Device Status screen and then click the Profile icon in the Icon Bar 7 The meter s Device Profile screen opens giving you access to the programmable settings for the meter NOTE A few basic settings are explained here Refer to the Shark 250 Meter Installation and Opera tion Manual and the Commu...

Страница 5: ...items in the list to redisplay this screen a CT Ratio enter Primary CT Numerator 1 9999 Secondary CT Denominator 5 or 1 Amp b PT Ratio enter Primary PT Numerator 1 9999 Secondary PT Denominator 1 9999 Example Settings For a CT of 2000 5 A set the following CT Ratios in the entry fields CT Numerator Primary 2000 CT Denominator Secondary 5 The Current Full Scale field will read 2000 For a system tha...

Страница 6: ...eld to configure when the meter will start reading values above 0 voltage e Total Demand Distortion TDD Setting This setting of the Device Profile allows you to set the maximum value for current which is used for the TDD Total Demand Distortion calculation TDD is an index used to measure harmonics In this field enter the maximum load current for TDD To disable TDD enter 0 in the field f CT Reversa...

Страница 7: ...ore responding to queries Parity Odd Even or None Program Meter Time The meter is preset to Eastern time To change the meter time 1 From the Main screen s Title bar click Tools Set Device Time 2 You can either enter the time in the Time fields or click Use PC Time to set the time using your PC s time 3 Click Send NOTE The meter offers multiple Time Synchronization methods See Chapter 28 Section 28...

Страница 8: ...me is used to name the log databases when logs are downloaded MPORTANT When you have made changes to the meter s Device Profile click Update Device at the top left of the Device Profile screen s Icon Bar to send the new settings to the meter The meter will reboot and then you can reconnect to it Shark is a registered trademark of Electro Industries GaugeTech The distinctive shape style and overall...

Отзывы: