Doc
#
E145701
2 - 10
2: Meter Overview and Specifications
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Max Input Wire Gauge:
AWG#12 / 2.5mm
2
Fault Withstand:
Meets IEEE C37.90.1
Reading:
Programmable Full Scale to any PT
Ratio
Current Inputs
Class 10:
5A Nominal, 10A Maximum
Class 2:
1A Nominal, 2A Maximum (Shark®
50 is Class 10 only)
Burden:
0.005VA Per Phase Max at 11 Amps
Pickup Current:
0.1% of Nominal
Connections:
O or U Lug Electrical Connection
(Figure 4.1)
Pass through Wire, 0.177" / 4.5mm
Maximum Diameter (Figure 4.2)
Quick Connect, 0.25" Male Tab
(Figure 4.3)
Fault Withstand (at 23
o
C): 100A/10sec.,
300A/3sec.,
500A/1sec.
Reading:
Programmable Full Scale to any CT
Ratio
Isolation
All Inputs and Outputs are galvanically isolated to 2500 VAC
Environmental Rating
Storage:
(-20 to +70)
o
C
Operating:
(-20 to +70)
o
C