6: Using the Shark® 100 Meter
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
CT Numerator (Primary): 1 - 9999
CT Denominator (Secondary): 5 or 1 Amp
NOTE:
This field is display only.
CT Multiplier: 1, 10 or 100
Current Full Scale: Calculations based on selections. Click
Recalculate
to see the
result of changes.
PT Ratios
PT Numerator (Primary): 1 - 9999
PT Denominator (Secondary): 40 - 600
PT Multiplier: 1, 10, 100, or 1000
Voltage Full Scale: Calculations based on selections. Click
Recalculate
to see the
result of changes.
System Wiring
3 Element Wye; 2.5 Element Wye; 2 CT Delta
Phases Displayed
A, AB, or ABC
NOTE:
Voltage Full Scale = PT Numerator x PT Multiplier
Example:
A 14400/120 PT would be entered as:
PT Numerator: 1440
PT Denominator: 120
Multiplier: 10
This example would display a 14.40kV.
Example CT Settings: