M.:
Date: Feb. 98
Page: 29
Vacuum Leak Detector
VL - H9
SGB
Sicherungsgerätebau
GmbH
57076 Siegen
8.3.4 Checking of the pump suction head
mbar
mbar
1000
1000
800
800
400
400
600
600
200
200
0
0
Measuring
Measuring
Exhaust
Exhaust
Suction
Suction
VL-H9-Ex and VL-H9/A-Ex
VL-H9/A-MV-Ex
The pressure switch is bled via the three-way valve (with the pump running), and the pressure
gauge is connected to the suction line. The interstitial space remains separated. Now, the
maximum pump suction head can be checked. It must be > 580 mbar.
In the case of the operation unit VL-H9/ME-MV-..., the starting switch must be in the starting
position.
Measuring line
Suction line
Shut-off cock on the tank
closed
closed
Position of the stop valves on the tank when checking the pump head
8.3.5 Leak test
mbar
mbar
1000
1000
800
800
400
400
600
600
200
200
0
0
Measuring
Measuring
Exhaust
Exhaust
Suction
Suction
VL-H9-Ex and VL-H9/A-Ex
VL-H9/A-MV-Ex
For carrying out the leak test, the pressure gauge is connected to the testing socket of the
measuring line. If the vacuum pump is running, wait until it switches off.
During 20 minutes,
the pressure should not significantly increase. Any leakage detected must be rectified, and the
test must be repeated.
Measuring line
Suction line
Shut-off cock on the tank
open
open
Position of the stop valves on the tank during the leak test.
5
If the pump is continuously running, the leakage must be rectified.
35 von 50