44
Operating Instructions – MOVITRAC® LTE-B
8
Advanced parameters
Parameters
8.2
Advanced parameters
P-12
Control via
terminals/keypad
/SBus
0
Terminal control
0
(terminal
control)
See section "Easy startup" (page 33).
1
Keypad control
(only forwards)
2
Keypad control
(to toggle between for-
wards/backwards, press the
<Start> key)
3
SBus network control with
internal acceleration/deceler-
ation ramps
4
SBus network control with
adjusted acceleration/decel-
eration ramp via bus.
P-13
Error log
The 4 most recent errors are
logged
No error
The last 4 errors are saved in chronological order.
The most recent error is displayed first. You can
view the saved errors by pressing the <Up/Down>
key. See section "Error codes" (page 40).
P-14
Advanced menu
access code
0 – 9999
0
"101" (standard) for advanced menu access.
Change the code in
P-37
to prevent unauthorized
access to the advanced parameter set.
1) 60 Hz (American variant only)
2) 460 V (American variant only)
Parameter Description
Range
Default
Explanation
P-15
Binary input func-
tion setting
0 – 12
0
Specifies the functions of the binary inputs. See
section "P-15 Functions of the binary inputs"
(page 48).
P-16
Analog input V /
mA
0 – 10 V, b 0 – 10 V, 0 – 20 mA
t 4 – 20 mA, r 4 – 20 mA
t 20 – 4 mA, r 20 – 4 mA
0 – 10 V
Configures the format of the analog input.
0 – 10 V: Unipolar mode (voltage input)
b 0 – 10 V: Bipolar mode (voltage input)
•
For bipolar input signals
•
50% offset with
P-39
•
200% scaling in
P-35
results in ±
P-01
0 – 20 mA: Unipolar mode (current input)
4 – 20 mA: Unipolar mode (current input)
20 – 4 mA: Unipolar return current mode
"t" = Inverter switches off if signal is revoked when
inverter is enabled.
"r" indicates that the inverter moves along the ramp
to the speed set in
P-20
.
P-17
PWM
2 – 16 kHz
4 / 8 kHz PWM setting.
A higher switching frequency means less motor
noise, but also higher losses in the output stage.
P-18
User relay output
selection
0 Inverter is enabled
1
(inverter
ok)
User relay settings. The threshold level is defined
in
P-19
.
Deactivated: Contacts open
Activated: Contact closed
1
Inverter ok (no error)
2
Motor at setpoint speed
3
Inverter is not enabled
4
Motor speed
≥
limit value
5
Motor current
≥
limit value
6
Motor speed < limit value
7
Motor current < limit value
P-19
Relay threshold
level
0 – 200% of maximum speed
P-01
or nominal motor current
P-08
100%
Specifies the limit value for
P-18
and
P-25
.
Parameter Description
Value range
Factory
setting
Explanation
P
i
f
kVA
Hz
n