Startup: Brief description
System Manual – MOVITRAC
®
B
47
Startup: Brief description
The frequency inverter MOVITRAC
®
B can be connected directly to a motor of the same
power. For example: A 1.5 kW motor can be connected directly to a MC07B0015.
Procedure
1. Connect the motor to the
MOVITRAC
®
B (terminal X2).
2. You have the option of connecting
a braking resistor (terminal X2).
3. The following signal terminals
must be controlled with your con-
trol system:
• Enable DI03
• As required: CW/STOP DI01 or
CCW/STOP DI02
• Setpoint:
– Analog input X10 and/or
– DI04 = n11 = 150 rpm
and/or
– DI05 = n12 = 750 rpm
and/or
– DI04 + DI05 = n13 = 1500
rpm
• For brake motors: DO02 =
brake control system using
brake rectifiers
4. You have the option of connecting
the following signal terminals:
• DI00 = error reset
• DO01 = /malfunction (designed
as a relay contact)
• DO03 = ready
5. Check the controller for required
functionality.
6. Connect the frequency inverter to
the mains (X1).
Notes
Signal terminal functions and setpoint settings can be modified using the FBG11B
keypad or a PC. A PC connection requires the FSC11B front option or one of the
following interface adapters: UWS21A / UWS11A / USB11A.
The MOVITRAC
®
B frequency inverter should only be operated in strict obser-
vance of the detailed operating instructions!
쓔
댷
쓔
Brake released*
}
n13 = n11 + n12
3-phase
24VIO
Enable/Rapid stop*
Error reset*
CW/Stop*
CCW/Stop*
Supply voltage for TF/TH*
+24 V Input/Output
Reference potential for binary signals
Reference potential
Reference potential
Ready for operation*
Relay contact /Malfunction*
Normally open contact relay
Normally closed contact relay
Shield clamp
Factory setting
Reference potential for analog signals
Switchover
I signal U signal*
3-phase
1-phase
REF1
GND
0
0
I