7
Technical data
MOVITRAC® B technical data
40
Operating Instructions Basic Unit – MOVITRAC
®
B
7.4.9
AC 400/500 V / 3-phase / size 2 / 11 kW / 15 HP
MOVITRAC
®
MC07B (3-phase supply system)
0110-5A3-4-00
Part number
828 527 6
INPUT
Permitted rated supply voltage
V
N
3 × AC 400 V
V
Mains
= AC 380 V – 10 % ... AC 500 V + 10 %
Rated supply frequency
f
N
50 / 60 Hz ± 5 %
Rated mains current 3-phase with
V
Mains
= AC 400 V
AC 21.6 A
OUTPUT
Output voltage
V
A
3 × 0 ... V
Mains
Recommended motor power under constant
load (with V
Mains
= AC 400 V)
P
Mot
11 kW
15 HP
Rated output current
with V
Mains
= AC 400 V
I
N
AC 24 A
Minimum permitted braking resistor value
(4-Q operation)
R
BW_min
22
Ê
GENERAL INFORMATION
Power loss at I
N
P
V
400 W
Current limitation
150 % I
N
for maximum 60 seconds
Connections
Terminals
4 mm
2
/ AWG12
Dimensions
W × H × D
130 × 335 × 229 mm / 5.1 × 13.2 × 9.0 in
Weight
m
6.6 kg / 14.6 lbs.
300
6.5
130
105
229
225
335
315
P
i
f
kVA
Hz
n