7
Technical data
General technical data
30
Operating Instructions Basic Unit – MOVITRAC
®
B
7.2
General technical data
The following technical data applies to all MOVITRAC
®
B frequency inverters, irrespec-
tive of size and power:
MOVITRAC
®
B:
All sizes
Interference immunity
Fulfills EN 61800-3
Interference emission with
EMC compliant installation
According to limit value class
•
1-phase connection:
A / B
•
3-phase connection:
A
– 230 V: 0.25 ... 7.5 kW
– 400/500 V: 0.25 ... 11 kW
According to EN 55011 and EN 55014; meets EN 61800-3
Leakage current
> 3.5 mA
Ambient temperature
â
A
•
230 V, 0.25 ... 2.2 kW / 400/500 V, 0.25 ... 4.0 kW
–10 °C... +50 °C at I
D
= 100 % I
N
and f
PWM
= 4 kHz
–10 °C... +40 °C at I
D
= 125 % I
N
and f
PWM
= 4 kHz
–10 °C... +40 °C at I
D
= 100 % I
N
and f
PWM
= 8 kHz
•
400/500 V, 5.5 ... 45 kW
0 °C ... +50 °C at I
D
= 100 % I
N
and f
PWM
= 4 kHz
0 °C ... +40 °C at I
D
= 125 % I
N
and f
PWM
= 4 kHz
0 °C ... +40 °C at I
D
= 100 % I
N
and f
PWM
= 8 kHz
•
Mounting platform with "cold plate" < 70 °C
Derating ambient
temperature
•
3% I
N
per K at 50 °C ... 60 °C
Climate class
EN 60721-3-3, class 3K3
Storage temperature
1)
Shipping temperature
1) If the unit is being stored for a long time, connect it to the mains voltage for at least 5 minutes every
2 years. Else, the unit's service life may be shortened.
–25 °C... +75 °C
–25 °C... +75 °C
Type of cooling
Self-cooled:
230 V:
Â
0.75 kW
400/500 V:
Â
1.1 kW
Forced cooled:
230 V:
Ã
1.1 kW
400/500 V:
Ã
1.5 kW
Enclosure
IP20
Operating mode
Continuous duty (EN 60149-1-1 and 1-3)
Overvoltage category
III according to IEC 60664-1 (VDE 0110-1)
Pollution class
2 according to IEC 60664-1 (VDE 0110-1)
Installation altitude
Up to h
Â
1000 m without restrictions.
At h
Ã
1000 m (3280 ft), the following restrictions apply:
•
From 1000 m (3280 ft.) to max. 4000 m (6561 ft.):
– I
N
reduction by 1 % per 100 m
•
From 2000 m (6,561 ft.) to max. 4000 m (13,123 ft.):
– AC 230 V units: V
N
reduction by AC 3 V per 100 m
(330 ft)
– AC 500 V units: V
N
reduction by AC 6 V per 100 m
(330 ft)
Over 2000 m only overvoltage class 2, external measures are
required for overvoltage class 3. Overvoltage classes according
to DIN VDE 0110-1.
Size 0:
Limitations for continuous
duty with 125 % I
N
•
Maximum ambient temperature
â
A
: 40 °C
•
Maximum supply voltage V
Mains
: 400 V
•
No DIN rail mounting / submounting resistor
•
with 1 x 230 V: Provide line choke ND
P
i
f
kVA
Hz
n