System Manual – MOVIDRIVE® compact Drive Inverters
395
11
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Operating displays of MCH42A (INTERBUS LWL)
Operation
INTERBUS-LWL
LEDs
The INTERBUS-LWL LEDs display the current status of the fieldbus interface and the
INTERBUS system:
The following figure shows the patterns of the INTERBUS-LWL LEDs that occur
frequently. The following tables explain the meanings of the LED patterns in more detail.
LED U
L
"U logic"
(green)
LED CC "Cable
check" (green)
LED BA "Bus
active" (green)
U
L
Logic voltage (green = OK)
CC
Cable check (green = OK)
BA
Bus active (green = OK)
RD
Remote bus disabled (red = OFF)
TR
Transmit (green = PCP active)
FO1
Fiber optic 1 (yellow = not OK)
FO2
Fiber optic 2 (yellow = not OK)
05226AEN
Figure 163: Frequent LED patterns
[A] Power-on of inverter (INTERBUS not yet active)
[B] Incorrect setting of DIP switches (INTERBUS not yet active)
[C] Initialization phase of INTERBUS system
[D] Correct INTERBUS operation
[E] Incorrect baud rate
State
Meaning
Remedy
On
Power supply of bus electronics
is present
-
Off
Power supply of bus electronics
is missing
Check that the connection unit is seated correctly and the
DC 24 V voltage supply for the inverter is applied.
State
Meaning
Remedy
On
Incoming remote bus
connection is functioning
properly
-
Off
Incoming remote bus
connection is faulty
Check the incoming fiber optic remote bus and the LED FO1.
State
Meaning
Remedy
On
Data transfer on the INTERBUS
is active
-
Off
No data transfer; INTERBUS is
stopped
Check the incoming fieldbus cable. Use the diagnostic
display on the INTERBUS interface module (master) to
localize the fault further.