244
System Manual – MOVIDRIVE® compact Drive Inverters
4
Supply system cables and motor cables
Project Planning
AC 230 V units metric, V
mains
= 3
×
AC 230 V:
Smallest wire
bending space
(EN 61800-5-1)
As stipulated in EN 61800-5-1, the distance between a power connection terminal and
an obstruction toward which the wire is directed on leaving the terminal must correspond
with the minimum values given in the table below.
MC_4_A...-2_3
0015
0022
0037
0055
0075
Size
1
2
Fuses F11/F12/F13
I
N
16 A
25 A
25 A
35 A
Mains conductor L1/L2/L3
1.5 mm
2
4 mm
2
4 mm
2
6 mm
2
PE conductor
2
×
1.5 mm
2
1
×
10 mm
2
2
×
4 mm
2
1
×
10 mm
2
2
×
4 mm
2
1
×
10 mm
2
2
×
6 mm
2
1
×
10 mm
2
Motor cable U/V/W
1.5 mm
2
4 mm
2
4 mm
2
6 mm
2
Unit terminal cross section
of the power section
Separable terminal strip
4 mm
2
conductor end sleeve DIN 46228
M4 screw with washer assembly with
terminal clip
4 mm
2
conductor end sleeve DIN 46228
6 mm
2
crimp cable lug DIN 46234
tightening torque
0.6 Nm
1.5 Nm
MC_4_A...-2_3
0110
0150
0220
0300
Size
3
4
Fuses F11/F12/F13
I
N
50 A
63 A
80 A
100 A
Mains conductor L1/L2/L3
10 mm
2
16 mm
2
25 mm
2
35 mm
2
PE conductor
1
×
10 mm
2
1
×
16 mm
2
1
×
16 mm
2
1
×
16 mm
2
Motor cable U/V/W
10 mm
2
16 mm
2
25 mm
2
35 mm
2
Unit terminal cross section
of the power section
M6 screw and washer assembly with washer
max. 25 mm
2
Crimp cable lug DIN 46234
M10 bolt with nut
max. 70 mm
2
Press cable lug DIN 46235
tightening torque
1.5 Nm
14 Nm
Cable cross section [mm
2
]
Smallest wire bending space [mm]
Wires per connection terminal
1
2
3
10 ... 16
40
-
-
25
50
-
-
35
65
-
-
50
125
125
180
70
150
150
190
95
180
180
205
120
205
205
230
150
255
255
280
185
305
305
330