Manual – MOVITRAC® B Communication Interface FSE24B EtherCAT®
45
8
Diagnostic procedures
Error Diagnostics
8
Error Diagnostics
8.1
Diagnostic procedures
The diagnostics procedures described in the following section demonstrate the fault
analysis methods for the following problems:
• Inverter does not operate on EtherCAT
®
• Inverter cannot be controlled using the EtherCAT
®
master.
For more information dealing specifically with the inverter parameter settings for various
fieldbus applications, refer to the "MOVITRAC
®
B Communication and Fieldbus Unit
Profile" manual and the MOVITRAC
®
B system manual.
Observe the notes regarding the voltage supply in chapter "Installing the communication
option FSE24B".
Step 1: Check the connection between the inverter and EtherCAT
®
Step 2: Response of the RUN LED?
Is the bus connected plugged into the master/inverter?
NO
→
[A]
YES
↓
What is the state of the
Link/activity
LED of the FSE24B option?
OFF
→
[A]
ON
↓
Is the physical connection between the inverter and EtherCAT
®
OK?
Make sure EtherCAT
®
is connected correctly at X30 IN (incoming
EtherCAT
®
connection) / X30 OUT (outgoing EtherCAT
®
connection).
NO
→
[A]
YES
↓
Continue with 2: Response of the RUN LED?
[A]
Check the bus cabling.
OFF
Has the master switched the slave to INIT state?
YES
→
NO
→
[A]
[B]
Flashing green
Slave is in PRE-OPERATIONAL state.
→
[C]
Lights up green
once
Slave is in SAFE-OPERATIONAL state.
→
[C]
Lights up green
Slave is in OPERATIONAL state.
→
[C]
[A]
Startup the bus in the master.
[B]
Option FSE24B is defective.
[C]
Continue with 3: Response of the ERR LED?