Manual – MOVITRAC® B Communication Interface FSE24B EtherCAT®
15
4
Status LEDs of FSE24B
Assembly and Installation Notes
Definition of display statuses
4.7.3
LED SYS-F (red)
The LED
SYS-F
(red) shows the status of the communication between the FSE24B front
module and MOVITRAC
®
B.
Display
Definition
Timeline
On
Display is switched on permanently.
Off
Display is switched off permanently.
Flickering
The display switches between on and
off with a frequency of 10 Hz.
3013055499
Flickering once
The display flickers once very shortly,
followed by an off phase.
3013416843
Flashing
Display switches on and off at a fre-
quency of 2.5 Hz (200 ms on, 200 ms
off).
3013456907
Flashing once
The display flashes once shortly (200
ms), followed by a longer off phase
(1000 ms).
3013459851
Flashing twice
The display flashes twice in quick suc-
cession, followed by an off phase.
3013463435
Flashing three
times
The display flashes three times in quick
succession, followed by an off phase.
3013466379
Flashing four
times
The display flashes four times in quick
succession, followed by an off phase.
3014762123
on
off
50ms
50ms
50ms
on
off
on
off
200ms
200ms
200ms
1s
on
off
200ms
1s
on
off
200ms
200ms
200ms
on
off
200ms
200ms
1s
200ms
200ms
200ms
on
off
200ms
200ms
1s
200ms
200ms
200ms
200ms
Condition
Error
Description
Off
No error
Communication between the FSE24B front module and
MOVITRAC
®
B is without faults.
On
No communication
No communication between the FSE24B front module and
MOVITRAC
®
B.
Check the P88. parameters in MOVITRAC
®
B:
•
Baud rate (CAN) = 500 kBd
•
Profile (CAN) = MOVILINK
®
•
SBus address = 0